PARAMETER 21 – IGNITION SEQUENCE SETTING
6. Use buttons ‘+’ o ‘-’ to modify the value of the
parameter between: min = value of parameter 17; max
= value of parameter 18.
The default value is:
- 90 Hz for Natural Gas;
- 110 Hz for propane;
7. Press and release button ‘S’ to confirm. The parameter
number (21) will appear in the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
P
ARAMETER 22 – FAN FREQUENCY VALUE DISPLAY
6. Use buttons ‘+’ o ‘-’ to modify the value of the parameter:
- 00 = Off
- 01 = On
If parameter value 01 is selected, during the water heater
operation, the display will show the fan frequency value
for 10 min.
7. Press and release button ‘S’ to confirm. The parameter
number (22) will appear in the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.