1507/1503
Users Manual
24
Model 1503
Output Voltage Display Range Resolution Test Current
Accuracy
± (% of Rdg + Digits)
0.1 to 20.00 M 0.01 M
20.0 to 200.0 M 0.1 M
500 V
(0 % to + 20 %)
200 to 500 M 1 M
1 mA @ 500 k ± (2.0 % + 5)
0.1 to 200.0 M 0.1 M
1000 V
0 % to + 20 %)
200 to 2000 M 1 M
1 mA @ 1 M ± (2.0 % + 5)
EN61557 Specification
The following tables are a requirement for European labeling.
Measurement Intrinsic Uncertainty Operating Uncertainty
1
Volts ± (2.0 % + 3) 30 %
Earth-Bond Resistance ± (1.5 % + 3) 30 %
Insulation Resistance
Depends on test voltage and range.
See Insulation Test specifications.
30 %
1. This specification comes from the standard and indicates the maximum amount allowable by the standard.

Other manuals for Fluke 1507