EasyManua.ls Logo

Fluke 76 - VDD (Series) Regulator Troubleshooting; Voltage Levels

Fluke 76
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
76
Service
3-16
Table 3-12. Voltage Levels
VDD
3.0 ± 0.2
VSS
3.2 ± 0.2
VBT- 6.1 (battery at full 9V charge)
3.2 (battery at low charge of 6.0V)
REFH
1.23 ± 0.04
PS0
1.23 ± 0.15
PS1
0 ± 0.15
VOA 2.2 to 1.7 (referenced from VSS)
VOB 1.07 to .85 (referenced from VSS)
Make the following tests:
1. Check for +1.23V ± 40 mV (Vrefh) at the cathode of VR1. If Vrefh is not correct,
check VR1, R19, R20, R21 and R44 carefully. If Vrefh is still incorrect, U4 is bad.
2. If Vrefh is correct, measure the voltage at U4 pin 6 (PS1). If Vps1 is not equal to 0V
± 0.15V, check R37 and R38. If Vps1 is still at an incorrect voltage, U4 is bad.
3. Check the bias generator circuit. With the exception of resistor R35 (620 kΩ), the
bias generator (which sets the bias level for all U4 analog circuitry) is internal to U4.
A problem with this circuit could cause the on-chip power supply op amps to fail.
Measure the dc voltage between U4 pin 8 (Vbias) and DGND. If -0.2V < Vbias <
+0.2V the bias generator is okay. If Vbias is not correct, check R35. If Vbias is still
wrong, replace U4.
4. Measure the ac voltage between Vdgnd and Vss. If it is greater than 10 mV ac, check
C21. (An open C21 causes common regulator instability.) The dc level may also be
incorrect.
5. If the common regulator still does not work, circuitry internal to U4 is bad. Replace
U4.
Vdd (Series) Regulator Troubleshooting 3-27.
If a problem still exists after the common regulator troubleshooting, continue with the
following Vdd regulator troubleshooting. Often, a short or sneak current path causes
power supply problems. Refer to the schematic for a diagram of the Vdd (Series)
Regulator. Make the following tests:
1. Measure the dc operating current from the 9V battery. If the current is greater than
1.2 mA, a sneak current path exists. A sneak current path can be very difficult to find.
2. First, visually check for both solder bridges on U4 pins and other circuit board shorts.
Isolate the current path at the negative battery terminal (Vbt-). The components
connected to Vbt- are C35, CR4, and R63. Remove these parts one at a time. Measure
I(bat) after each removal to isolate the problem.
1. If the excess battery current stops after removing R63, either R63, R57, Q9, or Q11
may be bad.
2. If the extra current is still present with all parts removed, remove Q10 and check for
excess battery current. If I(bat) is now correct, Q10 is bad. If I(bat) is still excessive,
U4 is probably at fault.
If the power supply is not working but battery current is normal, perform the following
tests.

Table of Contents

Other manuals for Fluke 76

Related product manuals