Appendix B: Test Method Names
Industry standards use different names for equivalent test
methods. Table B-1 shows the names used in this manual
and by four common industry standards for the three fiber
test methods
Table B-1. Test Method Names
Link End Connections
Included in Loss Results
This
Manual
TIA/EIA-526-14A
(multimode)
TIA/EIA-526-7
(singlemode)
IEC 61280-4-1
(multimode)
IEC 61280-4-2
(singlemode)
1 connection 2 Jumper Method A Method A.2 Method 1 Method A2
2 connections 1 Jumper Method B Method A.1 Method 2 Method A1
None 3 Jumper Method C Method A.3 Method 3 Method A3