Fluke i310s - Specifications; Electrical Characteristics

Fluke i310s
9 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Distributor of Fluke Electronics: Excellent Integrated System Limited
Datasheet of I310S - CURRENT PROBE AC/DC
Contact us: sales@integrated-circuit.com Website: www.integrated-circuit.com
i310s English Instruction Sheet
Page 3
CAT III equipment is designed to protect against
the transients in the equipment in fixed
equipment installations, such as distribution
panels, feeders and short branch circuits, and
the lighting systems in large buildings.
Do not use Clamp in wet environments or in
locations that hazardous gases exist.
Specifications
Electrical Characteristics
All accuracies stated at 23°C ± 1°C (73.4 °F ± 33.8 °F)
Current Range
30 A and 300 A ac rms or
± 45 A and 450 A dc
Inrush Current 600 A ac rms Max
Output Sensitivity
10 mV/A (30 A)
1 mV/A (300 A)
Accuracy
(30 A range) ± 1 % of reading ± 50 mA
(300 A range) ± 1 % of reading ± 300 mA
@25 °C, Bandwidth dc to 1 kHz
Bandwidth to Meet
Accuracy
Specification
1 kHz
Phase Shift below 1
kHz
< 2 degrees
Resolution
± 50 mA (30 A)
± 100 mA (300 A)
Load impedance > 10 k Ω and 100 pF
Conductor Position
Sensitivity
± 1.5 % relative to center reading
Frequency Range
(small signal)
DC to 20 kHz (-3 dB)
Temperature
Coefficient
± 0.01 % of reading / °C
Power Supply 9 V Alkaline, NEDA 1604/PP3 IEC 6LR61
Working Voltage 300 V ac rms or dc
Battery Life 30 hours, low battery indicator