Issue/Rev. 0.2 (6/14)
Page 14 AB06069
Appendix – Troubleshooting TCP/IP Communications
Appendix I – Troubleshooting TCP/IP Communications
Troubleshooting an Ethernet Connection
LED Indicators
The Link indicator on the Ethernet port (the green LED in top corner of AccuLoad.net main [KDC.NET] board)
is a simple indication of the correct wiring of the physical connection. Most PC and router ports also have a
visible indicator when the connection is wired properly. If the Link light does not illuminate, either the cable is
the wrong type (i.e. a standard CAT-5 cable was used when a crossover cable is needed or vice versa), the cable
is faulty, or one of the RJ45 connector plugs is not inserted completely into the jack. It is also possible but
unlikely that one of the device ports has failed. Eliminate the simplest first: double-check that the plugs are
inserted fully; and that the cable type is correct. You can often verify that a cable is standard (or not) by holding
the two connectors from each end of the cable together and viewing the wire colors within (most RJ45
connectors are clear plastic). If the color pattern on the wires is identical on both ends of the cable, it is a
standard cable.
PING Utility
To check the connection, Windows and most other networkable computers provide a low-level utility
called PING that issues a simple ICMP message to a remote device and awaits a response. To use this utility
in Windows, open a Command Prompt (DOS box) and type the command:
C:> PING ["UNIT ADDRESS"]
C:> PING 192.168.0.1
If the connection is successful, PING will report the total time from command to response. If it fails, a timeout
message will be displayed.
Advanced – Ethernet Diagnostic (Packet Sniffer) Utility
A useful tool for troubleshooting network communications is a packet sniffer. This type of utility provides a
mechanism to display the traffic being sent/received from the Ethernet port, and to dig down to the lower levels
to view MAC addresses and IP packet data.
An open source implementation of a packet sniffer utility, Wireshark (formerly Ethereal), is available and can be
downloaded from the Web at http://www.wireshark.org/. There are versions for Windows, Linux and other
platforms as well.
Troubleshooting a SLIP Connection
Using the Comm Monitor Diagnostic
The AccuLoad.net has a built-in diagnostic that displays traffic on the serial communications ports. To access
the Comm Monitor diagnostic, select Diagnostics Menu from the Main Menu, then scroll using the arrow keys
until the Comm Monitor selection is highlighted and press <Enter>. Then select the communications port
(1-3) that was configured for the SLIP connection. By examining the traffic it is possible to determine if data
is being received from the PC end, and whether a response is being issued. You can ‘freeze’ the display, and
scroll back and forth, and toggle ASCII and hex mode views of the last 255 characters in the communications
buffer.
CLIENT/CLIENTSERVER Handshake
When establishing a SLIP connection between two devices, Windows uses a non-standard handshake to
verify the device on the other end of the connection is compatible. Windows opens the port and immediately
sends the text “CLIENT” out the port, then waits for a response. Only the response “CLIENTSERVER” will be
accepted by Windows and allow the connection to be made. This handshake should happen quickly and it will
be visible on the Comm Monitor at least briefly if all is functioning properly. If the Comm Monitor shows repeated
CLIENT messages with no CLIENTSERVER response, it is possible you have the IP addresses incorrect on
one side or the other. The host PC’s IP address should be different than the AccuLoad.net, but again both
addresses must be on the same network.
Example: Where unit address is the IP Address of ALIII.
Question and Answer IconNeed help?

Do you have a question about the FMC Technologies Smith Meter AccuLoad III.net and is the answer not in the manual?

FMC Technologies Smith Meter AccuLoad III.net Specifications

General IconGeneral
ModelAccuLoad III.net
ManufacturerFMC Technologies Smith Meter
CategoryMeasuring Instruments
Enclosure RatingNEMA 4X
DisplayLCD
ApplicationLiquid Measurement and Control
Operating Temperature-40°C to +60°C (-40°F to +140°F)
Communication ProtocolModbus, Ethernet
Power Supply24 VDC or 120/230 VAC
Flow Rate RangeVaries depending on meter and application

Summary

Introduction to TCP/IP Communications and Basic Networking

TCP/IP Protocol Overview

Defines TCP/IP as the standard protocol for Internet communications.

Ethernet Basics

Explains Ethernet as a low-level protocol for hardware link between devices.

Network Addressing Concepts

Details IP Address, Net Mask, MAC Address, and Gateway definitions.

Connecting via Ethernet

AccuLoad.net Ethernet Configuration Steps

Step-by-step guide to configure AccuLoad.net network settings.

Network Topology Recommendation

Suggests using a private network for AccuLoad.net connections.

Windows XP Ethernet Connection Setup

Lists requirements and connection methods for PC setup.

Physical Ethernet Connection Methods

Explains machine-to-machine vs. hub connection methods.

Initiating PC Network Connection Setup

Guides user to access Windows Network Connections.

Configuring TCP/IP Properties in Windows

Details setting IP address, subnet mask, and gateway in Windows.

Configuring a SLIP Connection

AccuLoad.net SLIP Configuration Settings

Configures AccuLoad.net serial ports for SLIP.

SLIP Host Interface Settings

Sets IP address, network, and gateway for SLIP.

Windows XP SLIP Connection Wizard Steps

Guides through creating a SLIP connection in Windows.

Configuring SLIP COM Port Baud Rate

Sets baud rate and other serial parameters for SLIP.

SLIP Dial-up Server and Protocol Settings

Selects SLIP server type and network protocols.

Assigning PC IP Address for SLIP

Sets PC IP address for SLIP connection.

Using the TCP/IP Link

Establishing and Verifying TCP/IP Connection

Steps to launch AccuMate and confirm connection status.

Accessing AccuLoad via Web and FTP

Using HTTP interface and FTP for file transfer.

Firmware Upgrade Procedure

Firmware Upgrade Overview and Key Requirements

Explains firmware upgrade process and necessary keys.

Procedure for Upgrading Firmware

Detailed steps for performing a firmware upgrade.

Specifying Firmware Upgrade Key File

Locating the .A3Key file for the upgrade.

Entering Access Code for Upgrade

Inputting the security access code to authorize upgrade.

Firmware Upgrade Troubleshooting Tips

Addresses common issues like AccuMate version, keys, and connection errors.

Firmware Upgrade Switch Settings

Explains DIP switch configurations for bootloader.

Troubleshooting TCP/IP Communications

Ethernet Connection Troubleshooting

Interpreting LEDs, using PING, and packet sniffers.

SLIP Connection Troubleshooting

Using Comm Monitor and diagnosing handshake/IP issues.

Checking PC Serial Port Settings

Verifying COM port parameters using command line tools.