aPbox Manual
24
NOTE
The length of the communication cables between the aPbox and the aGate
shall not exceed 328 feet (100 meters)
Use twisted pair cables for RS485 conductors.
Refer to Table 1 above for wire gauge recommendations.
Two RC65s connected to an aGate
The FHP system supports up to two RC65 connections to a single aGate. When two RC65
units are connected in parallel to an aGate:
First RC65
o TB3 485A connected to the aGate A4 terminal
o TB3 485B connected to the aGate B4 terminal
Second RC65
o TB3 485A connected to the aGate A1 terminal