Franklin Home Power
Quick Installation Guide
Version 1.0

Other manuals for FRANKLINWH aPower X

Question and Answer IconNeed help?

Do you have a question about the FRANKLINWH aPower X and is the answer not in the manual?

Summary

Product Information

Tools

Torque Requirements

Specifies screw types and their corresponding tightening torques for installation.

Installation Requirements

Installation Environment

Details the conditions for installing aPower X and aGate X units indoors or outdoors.

General Safety Precautions

Highlights critical safety warnings for handling and installation to prevent injury or damage.

Installation Method

Installation Space

Defines recommended clearances for aGate X and aPower X units during installation.

Cable Specifications and Installation Warnings

Maximum Cable Lengths

Specifies maximum allowable cable lengths for various data exchange devices.

Drilling Safety Precautions

Warns against drilling into water pipes/cables and protecting heat dissipation holes.

Introduction to the aGate X

aGate X Component Overview

Identifies and describes the various terminals and modules within the aGate X.

Power Connection Warning

Emphasizes correct connection of power sources to corresponding FHP ports.

aGate X Panel Removal

Remove the Inner Panel

Instructions on how to remove the inner panel using specific screwdrivers.

Remove the Door

Instructions on how to remove the door using specific screwdrivers.

Mount the aGate X on a Wall

Sealing Washers and Knockouts

Notes on installing sealing washers and selecting knockouts/plugs for conduit entry.

Drilling and Dust Protection Warnings

Safety warnings regarding drilling into walls and protecting components from dust.

aPower X Accessory Removal

Remove External Cables

Instructions to open the wiring compartment and remove the 3 external cables.

Remove Water-Proof Lock

Guide on removing the water-proof lock using an adjustable wrench.

Remove Lower Plug for Signal Cable

Instructions for removing the lower plug if a signal cable hole is needed.

Cable Connection Regulations

Warning to connect cables in accordance with local installation laws and regulations.

Installing the aPower X

M6 Spacer for Bracket Installation

Instruction to add an M6 spacer to each bolt when installing the bracket.

Special Wall;Baseboard Installation Methods

Provides solutions for installing aPower X on concave, protruding, or uneven walls.

Breaker and Optional Parts

Standard Configuration

Illustrates the standard configuration of breakers and modules.

Full Configuration

Shows the full configuration including optional Smart Circuits and Generator Modules.

Communications Wiring

Com Kit Activation

Connect a Com Kit (4G & Wifi) cable to activate aGate X commissioning functions.

Communications Cable Preparation

Steps for preparing communication cables including wiring order and crimping.

Network Connection for Remote Access

Connect aGate X to the network via Eth2 port for remote FHP access.

aGate X and aPower X Communications Connection

Cable Length Considerations

Details when to use a communications cable or 20V power supply based on length.

Parallel aPower X Units

Instructions for removing excess matching terminals when multiple aPower X units are in parallel.

Shared Conduit Wiring

Guidance on using Type 600V TC insulated cable for shared conduits.

20 V Power Supply Connection

Steps for connecting the 20V power supply to the terminal.

Power Wiring Diagram

Solar Inverter Connections

Diagram and warning for connecting solar inverters to the aGate X.

Smart Circuit Connections

Diagrams for connecting single-pole and double-pole smart circuits.

AC and Generator Power Connections

Grid AC Power Connections

Illustrates grid AC power connections to the aGate X, noting L1/L2 swapping.

Generator Power Connections

Shows generator power connections to the aGate X, including GEN terminals.

Aluminum Cable Treatment

Note on treating aluminum cable connectors with antioxidant.

aPower X to aGate X Connections

Single aPower X Unit Connection

Diagram showing wiring for one aPower X unit connected to the aGate X.

Multiple aPower X Units to aGate X

2 to 3 aPower X Units

Wiring diagram for connecting 2 to 3 aPower X units to the aGate X.

WAGO Terminal Wire Gauge

Warning that WAGO terminals accept only 10AWG power wire.

Connecting More Than 3 aPower X Units

Backup Load Terminals Usage

Guidance on using backup load terminals for more than 3 aPower X units.

WAGO Terminal Wire Gauge

Warning that WAGO terminals accept only 10AWG power wire.

Re-installation Procedures

aPower X Cover Re-installation

Steps for re-installing the aPower X cover.

aPower X Grills Installation

Instructions for installing the aPower X grills.

aGate X Panel Re-installation

Steps for re-installing the aGate X door and inner panel.

Conduit Diagram

FHP System Activation with Smartphone App

App Download and Setup

Instructions for searching, downloading, and signing up for the FranklinWH app.

Installer Account Login

Steps for installer login to set FHP parameters and bind homeowner accounts.

Homeowner Account Login

How to log into the homeowner account to view system data.

Overview

The Franklin Home Power (FHP) system, comprising aPower X and aGate X units, is a comprehensive energy storage solution designed for residential use. This Quick Installation Guide outlines the setup, technical specifications, and operational aspects of the system, ensuring reliable and efficient energy management.

Function Description

The Franklin Home Power system integrates solar power, grid electricity, and battery storage to optimize energy usage in a home. The aPower X units are the battery storage components, while the aGate X acts as the central control and switching device, managing the flow of power between the grid, solar inverter, aPower X units, and household loads. This intelligent system allows homeowners to store excess solar energy, use stored energy during peak hours or power outages, and reduce reliance on the grid. The system supports both floor-mounted and wall-mounted installations for aPower X, and wall-mounted or embedded installations for aGate X, offering flexibility in placement. The FHP system can be activated and monitored via a smartphone application, providing real-time data on energy flow and system status.

Important Technical Specifications

  • Torque Requirements for Screws:
    • M4 (PH2 screwdriver): 1.03 lbf·ft (1.4 N·M)
    • M5 (PH2 screwdriver): 2.21 lbf·ft (3.0 N·M)
    • M6 (PH3 screwdriver): 4.42 lbf·ft (6.0 N·M)
  • Maximum Cable Lengths for Data Interchange:
    • aPower X and aGate X: 98.4 ft (30 m)
    • aGate X to Generator: 98.4 ft (30 m)
    • aGate X to Router: 328.1 ft (100 m)
    • External CT: 16.4 ft (5 m)
  • aGate X Terminal Max Current Ratings:
    • Solar terminal: 80A
    • aPower terminal: 100A
    • Smart Circuits 1, 2: 50A
    • Smart Circuit 3: 80A
    • Grid terminal: 200A
    • Generator terminal: 200A
    • Bonding jumper: 280A
    • Non-backup load terminals: 160A
    • Backup load terminals: 160A
    • Combiner box terminal: 30A
  • Installation Space Requirements:
    • aGate X: Minimum clearance of 5D (D = outer diameter of electrical conduits) from bottom to floor and top to ceiling. Recommended distance from bottom to ground: 48 in. (1.22 m), not exceeding 64 in. (1.63 m). Maximum distance from power switch button to ground: 90 in. (2.29 m).
    • aPower X: Minimum clearance of 5D from top to ceiling. Recommended distance from bottom of mounting bracket to ground: 19.7 in. (0.5 m), not exceeding 54.25 in. (1.38 m). Maximum distance from switch button to ground: 90 in. (2.29 m).
    • Multiple aPower X units: Recommended distance between units: 12 in. (0.3 m), minimum: 6 in. (0.15 m).
    • Frontal clearance: 72 in. (1.83 m) in front of the wall in the installation area.
  • Noise Factor: Less than 45dB for each aPower X unit.
  • Power Wire for WAGO Terminals: 10AWG for each aPower X.
  • Communication Cable: If sharing conduit with power wires, use Type 600V TC insulated communication cable (with metal connector).

Usage Features

  • Flexible Installation: Both aPower X and aGate X units can be installed indoors or outdoors. Outdoor installations require a sheltered location protected from direct exposure to sun, rain, and snow.
  • Scalable System: The FHP system supports multiple aPower X units, allowing for expansion of energy storage capacity. Connections for up to 15 aPower X units are detailed, with specific instructions for connecting more than 3 units via a combiner box.
  • Smart Energy Management: The aGate X serves as the intelligent control center, managing power flow from solar, grid, and battery storage. It includes terminals for solar, grid, generator, and various smart circuits, enabling comprehensive home energy integration.
  • Remote Monitoring and Control: The FranklinWH smartphone app allows homeowners to activate the system, monitor real-time energy data (solar generation, FHP usage, grid interaction), and view the running status of energy devices. Installers can use the app for initial setup and parameter configuration.
  • Generator Integration: The aGate X supports connection to a generator, providing an additional layer of backup power. Signal exchange between the generator and aGate X may be required, referring to the generator's manual.
  • Smart Circuit Support: Optional Smart Circuits Modules can be integrated into the aGate X to manage specific loads within the home.

Maintenance Features

  • Clear Installation Guidelines: The manual provides detailed instructions for removing and reinstalling components like the aGate X inner panel and door, facilitating access for wiring and maintenance.
  • Safety Warnings: Emphasizes the importance of personal safety, requiring PPE during transfer and installation. Warnings are provided against drilling into water pipes or buried cables, and protecting aPower X heat dissipation holes during drilling.
  • Cable Management: Instructions for preparing communication cables (568B standard) and testing them with a wire tracker are included to ensure correct wiring and prevent issues.
  • Structural Engineering Compliance: Final installation methods and spacing must comply with licensed Structural Engineering Design, ensuring structural integrity and safety.
  • Local Codes and Standards: All installations must comply with local codes and standards, including NFPA 70-250 Grounding and Bonding Part V for service equipment installations.
  • Product Protection: Advises using protective measures (foam, cloth) to prevent damage to aPower X and aGate X during handling.
  • Disposal Information: Provides guidance on the proper disposal of scrapped products, emphasizing adherence to local laws and regulations for environmental protection.
  • Technical Support: For complex configurations, such as connecting more than 3 aPower X units, users are advised to consult FranklinWH for technical support.
  • Warranty Information: Users are directed to the Franklin Home Power Limited Warranty document for detailed information on warranty eligibility.