FR500A&FR510A Series Vector Control Inverter
- 1 -
Preface
Thank you for choosing FRECON developed and produced FR500A&FR510A series
vector control inverter.
FR500A&FR510A series vector control inverter is mainly positioned as a high-end market for
OEM customers and the specific requirements of fan and pump load applicationsits flexible design,
both embedded SVC and VF control in one, can be widely used for speed control accuracy, torque
response speed, low-frequency output characteristics and other situations with higher requirements.
This user manual supplies a detailed description of FR500A &FR510A series vector control
inverter includes product characterization, structural features, parameter setting, operation and
commissioning, inspection maintenance and other contents. Be sure to carefully read through the
safety precautions before use, and use this product on the premise that personnel and equipment
safety is ensured.
IMPORTANT NOTES
To illustrate the details of the productspictures in this manual based on products with outer
casing or safety cover being removed. When using this product, please be sure to well install
outer casing or covering by the rules, and operating in accordance with the manual contents.
The illustrations this manual for illustration only and may vary with different products you have
ordered.
The company is committed to continuous improvement of products, product features will
continue to upgrade, the information provided is subject to change without notice.
If you are using have questions, please contact our regional agents or our customer service
center. Customer Service Tel 0755 -33067999.
The company's other products please visit our website. http://www.frecon.com.cn

Table of Contents

Questions and Answers

  • C
    Clinton SpencerSep 4, 2025
    What causes a Frecon FR500A-4T-045G/055P to display Inverter overload and how to resolve it?
    • M
      marie92Sep 4, 2025
      An 'Inverter overload' error on your Frecon Inverter can be caused by a load that is too heavy or a locked-rotor condition on the motor. In this case, reduce the load and check the motor and mechanical condition. Another possible cause is that the AC drive model is of too small a power class, so you may need to select an AC drive of higher power class.
  • Z
    Zachary LopezSep 18, 2025
    What does PID feedback loss mean on Frecon FR500A-4T-045G/055P?
    • S
      samanthajacksonSep 18, 2025
      A 'PID feedback loss' in Frecon Inverter means that PID feedback set value is less than F13.24, so check the PID feedback signal or set to an appropriate value F13.24.
  • J
    Joshua HuffSep 16, 2025
    What causes Motor auto-tuning fault in Frecon FR500A-4T-045G/055P Inverter?
    • T
      Tiffany WatsonSep 16, 2025
      A 'Motor auto-tuning fault' in Frecon Inverter is caused by the motor and the inverter output terminals are not connected, so check the connection between the inverter and motor. Also, the motor does not disengage the load, so the motor is disengaged load. The electrical fault, so check the motor.
  • C
    connie40Sep 14, 2025
    What does Braking unit fault mean on Frecon FR500A-4T-045G/055P?
    • M
      madison32Sep 15, 2025
      A 'Braking unit fault' in Frecon Inverter means that the brake line failure or damage the brake pipe, so check the brake unit, replace the brake pipe. Also, an external braking resistor is too small, so increasing the braking resistor.
  • K
    kevin67Sep 13, 2025
    What does Communication overtime error mean on Frecon Inverter?
    • S
      Shannon RojasSep 13, 2025
      A 'Communication overtime error' in Frecon Inverter means that PC is not working properly, so check the PC Connection. Also, the communication line is not normal, so check the communication cable. The communication parameters F15 are set incorrectly, so the communication parameters are set correctly.
  • A
    amandalittleSep 12, 2025
    What does EEPROM read/write fault mean on a Frecon FR500A-4T-045G/055P?
    • J
      Jessica RodriguezSep 12, 2025
      An 'EEPROM read/write fault' on a Frecon Inverter indicates that the EEPROM chip is damaged. To resolve this, replace the main control board.
  • K
    Kelsey TuckerSep 9, 2025
    What should I check if my Frecon FR500A-4T-045G/055P Inverter reports Power output phase loss?
    • M
      Matthew Patel Jr.Sep 9, 2025
      If your Frecon Inverter reports a 'Power output phase loss' error, start by checking the cable connecting the AC drive and the motor for any faults and eliminate them. Also, check whether the motor's three-phase winding is normal, as unbalanced AC drive three-phase outputs when the motor is running can cause this issue.
  • J
    John SavageSep 7, 2025
    What does Module overheat mean on my Frecon FR500A-4T-045G/055P Inverter and how do I fix it?
    • C
      crystalorozcoSep 7, 2025
      A 'Module overheat' error on your Frecon Inverter indicates that the module is overheating. This could be due to several reasons: the ambient temperature might be too high, so lower it. The air filter might be blocked, so clean it. The fan might be damaged, so replace it. The thermally sensitive resistor of the module might be damaged, so replace it. Or, the inverter module itself might be damaged, so replace it.
  • M
    michael60Sep 5, 2025
    How can I fix a Power input phase loss error on my Frecon FR500A-4T-045G/055P Inverter?
    • H
      harrisgarySep 6, 2025
      To address a 'Power input phase loss' error on your Frecon Inverter, first check if the three-phase power input is abnormal and eliminate any external faults.
  • C
    Courtney WhitakerAug 21, 2025
    What to do if my Frecon FR500A-4T-045G/055P shows Accel overcurrent?
    • L
      Lisa BergerAug 21, 2025
      If your Frecon Inverter displays an 'Accel overcurrent' error, it could be due to several reasons. First, check for any grounding or short circuits in the output circuit and eliminate those faults. If the acceleration time is too short, increase it. Also, ensure that your manual torque boost or V/F curve settings are appropriate and adjust them if necessary. Low voltage can also trigger this error, so adjust the voltage to the normal range. If you're starting the motor while it's rotating, either select rotational speed tracking restart or wait for the motor to stop before starting. Remove any sudden loads added during acceleration. Finally, if the AC drive model is too small, select a higher power class AC drive.

Summary

Chapter 1 Safety Precautions

1.1 Safety Considerations

General safety considerations for installation, wiring, and operation.

Chapter 2 Product Information

2.3 Technical Features

Detailed technical specifications and features of the inverter.

Chapter 3 Installation and Wiring

3.2 Installation Direction, Space and Cooling

Guidelines on inverter mounting orientation, required space, and cooling.

3.8 Terminal Configuration

Schematic diagrams of main circuit and control circuit terminals.

Chapter 4 Operation and Display

4.2 Viewing and Modifying Function Codes

Procedures for navigating and changing function codes and parameters.

Chapter 5 List of Parameter

5.2 Standard Function Parameters

Table listing standard function parameters, their ranges, and defaults.

Chapter 6 Specification of Parameters

Group F00 System Parameters

System parameters group for inverter configuration.

Group F00 System Parameters

Group F10 Vector Control Parameters of Motor 1

Group F11 Protection Parameters

Group F13 Process PID

Appendix B: Braking Resistor

Frecon FR500A-4T-045G/055P Specifications

General IconGeneral
ModelFR500A-4T-045G/055P
CategoryInverter
Rated Power45kW/55kW
Protection LevelIP20
Cooling MethodForced Air Cooling
Communication InterfaceRS485

Related product manuals