QUANTUM
LX CONDENSER/VESSEL CONTROL PANEL
MAINTENANCE
090.560-M (MAY 2016)
Page 49
ANALOG BOARD SETTINGS
COMMUNICATIONS
The following table is to be used when conguring the Quantum™ for external communications.
LK1
In 120 ohm long communications line termination.
Out * No termination.
* default setting
MISCELLANEOUS
LK2
In
Not Used
Out *
LK3
In
Not Used
Out *
LK4
In
Not Used
Out *
* default setting
NOTE: Although LK2, 3 and 4 are not used, they must still be set for the default positions.
DIPSWITCH SETTINGS
The following table is to be used to set the analog board addresses. Refer to and study the diagram at the bottom of this page to
determine the correct board conguration.
Condenser Analog Board DIP Switch Settings
Analog
Board #
SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8
1 Off Off Off Off Off Off Off Off
Vessel Analog Board DIP Switch Settings
Analog
Board #
SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8
2
On Off Off Off Off Off Off Off
Condenser Panel
Vessel Panel
Analog Board 1
(Standard)
+Rx/+TX
-Rx/-TX
Analog Board 2
(Standard)
+Rx/+TX
-Rx/-TX
Communications
Terminal Blocks
Inside Panel
Communications
Terminal Blocks
Inside Panel
Digital Board 5
(Optional)
Digital Board 4
(Standard)
Digital Board 2
(Optional)
Digital Board 1
(Standard)