104 PB
TROUBLESHOOTING
E36 Error
See Figure 701
Does n wiring
meet specicaons?
14 gauge stranded wiring rated
for 600v
Replace wiring
as required.

Are there any junc boxes or
splices in the wiring except for
code required disconnects?

Replace wiring
as required.
Yes
Is Wiring connected to the
proper terminals?
L, N, S1 are not always
cgured from  to right.
No
Correct wiring
connecs.

Check Line Voltage at indoor
and Outdoor Units for 115 or
230 VAC as required.
Is voltage correct?
Trace back
source of
problem and
correct.


Is condensate pump being
powered from terminal block?
It must have it’s own power
source.
Connect
condensate
pump to its
own power
source.
Yes
Yes
Measure voltage between S1
and N. Is the voltage ng
between 0 and 24 vdc?


Replace indoor
or outdoor
control boards
as required.
No
E36 Error
Check the indoor and outdoor
fan motors. See Component
Tes secon. Do motors
check good?
Replace motor
as required
End
Yes
No




Table of Contents

Other manuals for Friedrich FPHMR36A3A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Friedrich FPHMR36A3A and is the answer not in the manual?

Friedrich FPHMR36A3A Specifications

General IconGeneral
BrandFriedrich
ModelFPHMR36A3A
CategoryAir Conditioner
LanguageEnglish

Related product manuals