6.12 Fan Control
Outline
Fan control is carried out according to the following priority.
1. Fan ON control for electric component cooling fan
2. Fan control when defrosting
3. Fan OFF delay when stopped
4. ON/OFF control in cooling operation
5. Tap control when drooping function is working
6. Fan control in forced operation
7. Fan control in indoor/outdoor unit silent operation
8. Fan control in powerful mode
9. Fan control in normal operation
Detail
Fan OFF Control when Stopped
* Fan OFF delay for 60 seconds must be made when the compressor is stopped.
Tap Control in indoor/outdoor unit silent operation
1. When Cooling Operation
When the outdoor air temperature is lower than 99°F, the fan tap must be set to L.
2. When Heating Operation
When the outdoor air temperature is higher than 39°F, the fan tap must be turned to L (only for heat pump model).
Frequency
Compressor
Four way valve
Fan
Electronic expansion
valve opening
ON
OFF
ON
OFF
ON
OFF
0Hz
5sec.
350pps 450pps450pps
Initial opening
PI control
5sec.
50sec.50sec. 600sec.
60sec.
Function and Control
35

Other manuals for Friedrich MR09C1H

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Friedrich MR09C1H and is the answer not in the manual?

Friedrich MR09C1H Specifications

General IconGeneral
BrandFriedrich
ModelMR09C1H
CategoryAir Conditioner
LanguageEnglish

Related product manuals