Max. ambient temperatures:
-40 °C / +55 °C
Relative humidity:
0-100%
The airflow within the invert-
er is from the left and right
to the top (cold air taken in
from the left and right, hot
air dissipated out of the top).
The exhaust air can reach a
temperature of 70 °C.
If the inverter is installed in a switch cabinet or a similar sealed area, then
forced-air ventilation must be provided to ensure adequate heat dissipation.
If the inverter is to be installed on the outer wall of a cattle shed, maintain a
minimum all-round clearance of 2 m between the inverter and all ventilation
and other openings in the building.
The installation location must not be exposed to ammonia, corrosive vapours,
salts or acids.