Technical Data - General
Nominal voltage (3-phase)
Operating range (class 1)
Operating range (class 2)
400 - 480 V
320 -552 V
173 - 400 VLL ± (2 % RDG/accuracy)
Nominal voltage (1-phase)
Operating range (class 1)
Operating range (class 2)
230 - 277 V
184 - 318,55 V
100 - 230 VLN ± (1 % RDG/accuracy)
Nominal frequency / Tolerance 50 - 60 Hz / 45 - 65 Hz
Nominal / Maximum current 1 A + 5 A / 6 A
Powerfactor range
(EN/IEC 62053-21, EN/IEC 62053-23)
aktiv cosφ 0.5 ind to 0.8 cap
reaktiv sinφ 0.5 ind to 0.5 cap
Current transformer ratio (kCT) 1 - 1000
e. g. TC 800/5A kCT = 160
for direct connection: kCT = 1
Voltage transformer ratio (kVT) 1 - 1000
e. g. VT 20000/400V kVT = 50
for direct connection: kVT = 1
Maximum value kVT x kCT 1000 (CT/5A)
Permitted ambient temperature from -25° to +65°C
Mounting DIN rail 35 mm
IP range (EN60529) IP54 / IP20 (Front / Connections)
Communication
Standard RS485 - 3 conductors
Protocol Modbus RTU
Min. Softwareversion Datamanager 2.0: 3.16.1 / Fronius Symo Hybrid:
1.16.1 / Fronius GEN24: 1.12.1
Screw terminal
Measuring input / neutral line 1 - 4 mm
Output (data communication /Auxiliary power supply) 0,05 - 2,5 mm
Recommended torque Measuring input: max. 0,6 Nm
Output / Auxiliary power supply: max. 0,4 Nm
Detailed, country-specific warranty terms are available on: www.fronius.com/solar/warranty