EasyManua.ls Logo

Fuji Electric frenic 5000g11s - Page 10

Fuji Electric frenic 5000g11s
41 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9
ACK response frame [Inverter
Host]
Value
Byte Field
ASCII type Hexadecimal
Description
0
SOH
SOH 01
H
Start of header
1 Station address ’0’–3’, ’9’
30
H
–33
H
, 39
H
Station address of inverter (Decimal:
×
10)
2 ’0’–’9’ 30
H
–39
H
Station address of inverter (Decimal:
×
1)
3
ACK
ACK
06
H
Transmission request
Acknowledge: When there are no receiving error and
logical error of the request
4 Command
‘R’
‘W’
‘A
‘E’
52
H
57
H
41
H
45
H
Answer back to request command
Polling (reading)
Selecting (writing)
High-response selecting (writing)
Alarm reset
5 Type
‘F’
’E’
‘C’
‘P’
‘H’
‘A
‘o’
‘S’
‘M’
46
H
45
H
43
H
50
H
48
H
41
H
6F
H
53
H
4D
H
Function type
Fundamental Functions
Extension Terminal Functions
Control Functions of Frequency
Motor Parameters
High performance Functions
Alternative Motor Parameters
Optional Functions
Setting data Functions
Monitoring data Functions
6 Function code ’0–’4’ 30
H
–34
H
Function code (Decimal:
×
10)
7 ’0’–’9’ 30
H
–39
H
Function code (Decimal:
×
1)
8 Polarity
‘ ’
‘-’
20
H
2D
H
Polarities of M09 and M35 data
Positive data, normal data (except M09 and M35)
negative data
9 Data ’0’–’F’ 30
H
–3F
H
1st character of data (Hexadecimal:
×
1000
H
)
10 ’0’–’F’ 30
H
–3F
H
2nd character of data (Hexadecimal:
×
100
H
)
11 ’0’–’F’ 30
H
–3F
H
3rd character of data (Hexadecimal:
×
10
H
)
12 ’0’–’F’ 30
H
–3F
H
4th character of data (Hexadecimal:
×
1
H
)
13
ETX
ETX 03
H
End of text
14 BCC ’0’–’F’ 30
H
–3F
H
Check sum 1 (Hexadecimal:
×
10
H
)
15 ’0’–’F’ 30
H
–3F
H
Check sum 2 (Hexadecimal:
×
1
H
)
SOH
Station address
ACK
Com-m
and
Type
Function code
Polarity
Data
ETX
BCC
0 1 2 3 4 5 6 7 8 9 12 13 14 15
1 2 1 1 1 2 1 4 1 2 (byte)
Area included to BCC

Related product manuals