24
5-4 Monitoring data
Code Description Unit Range Min. unit
Read/Write
M01 Setting frequency
(Final data)
- -20000–20000
(Maximum frequency at
±
20000)
1 R
M05 Setting frequency
(Final data)
Hz 0–400.00 (P11S: 0.00–120.00) 0.01 R
M06 Output frequency 1 - -20000–20000
(Maximum frequency at
±
20000)
1 R
M07 Torque calculation value % -200.00–200.00 0.01 R
M08 Torque current % -200.00–200.00 0.01 R
M09 Output frequency 1 Hz
0.00–400.00 (P11S
0.00–120.00 )
0.01 R
M10 Input power % 0.00–200.00 0.01 R
M11 Output current % 0.00–200.00 (Inverter rating at 100.00) 0.01 R
M12 Output voltage V 0.0–600.0 1.0 R
M13 Operation command
(Final data)
- Refer to the data format [14] - R
M14 Operating state - Refer to the data format [16] - R
M15 Y1-Y5 output terminal data - Refer to the data format [15] - R
M16 Fault memory 0 -
M17 Fault memory (1st prior) -
M18 Fault memory (2nd prior) -
M19 Fault memory (3rd prior) -
Refer to the data format [10] - R
M20 Operating time h 0–65535 1 R
M21 DC link circuit voltage V 0–1000 1 R
M23 Type code - Refer to the data format [17] - R
M24 Capacity code - Refer to the data format [11] - R
M25 ROM version - 0–64999 1 R
M26 Transmission error code - Refer to the data format [10] - R
M27 Setting frequency at alarming
(Final data)
- -20000–20000
(Maximum frequency at 20000)
1 R
M31 Setting Frequency at alarming
(Final data)
Hz 0–400.00 (P11S: 0.00–120.00) 0.01 R
M32 Output frequency at alarming - -20000–20000
(Maximum frequency at
±
20000)
1 R
M33 Torque calculation value at alarming % -200.00–200.00 0.01 R
M34 Torque current at alarming % -200.00–200.00 0.01 R
M35 Output frequency 1 at alarming Hz -400.00–400.00
(P11S: -120.00–120.00)
0.01 R
M36 Input power at alarming % 0.00–200.00 0.01 R
M37 Output current at alarming % 0.00–200.00 (Inverter rating at 100.00) 0.01 R
M38 Output voltage at alarming V 0.0–600.0 1.0 R
M39 Operation command at alarming - Refer to the data format [14] - R
M40 Operating state at alarming - Refer to the data format [16] - R
M41
Y1-Y5 output terminal data at alarming
- Refer to the data format [15] - R
M42 Operation time at alarming h 0–65535 1 R
M43 DC link circuit voltage at alarming V 0–1000 1 R
M44
Inverter internal air temp. at alarming
°
C
0–120 1 R
M45 Cooling fin temp. at alarming
°
C
0–120 1 R
M46 Life of main circuit capacitor % 0.0–100.0 0.1 R
M47
Life of printed circuit board capacitor
h 0–65535 1 R
M48 Life of cooling fan h 0–65535 1 R
Note :
1) The output frequency 1 is before slip compensation.
2) The output frequency 1 with speed regulator (using option OPC-G11S-PG) is treated as the
synchronous frequency.

Related product manuals