2-8
Control circuit terminals
Table 2.5 Names, Symbols and Functions of the Control Circuit Terminals
Classifi-
cation
Name
Symbol
Functions
Analog
input
Analog setting voltage input
[12]
External voltage input that commands the frequency externally.
(1) Input voltage range : 0 to ±10VDC / 0 to ±100%
(2) Hardware specifications
Input impedance : 22 kΩ
The maximum input voltage is ±15VDC, however, more than ±
15VDC is regarded as ±10VDC.
Analog setting voltage input
Analog setting current input
[V2]
(V2/C1)
External voltage input that commands the frequency externally.
(1) Input voltage range : 0 to ±10VDC / 0 to ±100%
(2) hardware specifications
Input impedance : 22 kΩ
The maximum input voltage is ±15VDC, however, more than ±
15VDC is regarded as ±10VDC.
External current input that commands the frequency externally.
(1) Input voltage range : 4 to 20mADC / 0 to 100%
(2) hardware specifications
Input impedance : 250 Ω
The maximum input current is 30mADC, however, more than
20mADC is regarded as 20mADC.
PTC/NTC thermistor input.
[NTC]
(PTC/NTC)
Connection of a PTC (Positive Temperature Coefficient) or NTC
(Negative Temperature Coefficient) thermistor for motor protection.
Analog common
[11]
Common terminal for analog input signals.
Digital
input
Digital input 1 to
Digital input 8
[X1]
[X2]
[X3]
[X4]
[X5]
[X6]
[X7]
[X8]
(1) Various signals such as "Coast to a stop," "Enable external
alarm trip," and "Select multi-frequency" can be assigned to
terminals [X1] to [X8], [FWD] and [REV] by setting function
codes E01 to E08, E98, and E99.
(2) Input mode, i.e. SINK and SOURCE, is changeable by using
the slide switch SW1.
(3) The logic value (1/0) for ON/OFF of the terminals [X1] to [X8],
[FWD], or [REV] can be switched. If the logic value for ON of
the terminal [X1] is "1" in the normal logic system, then OFF is
"1" in the negative logic system and vice versa.
(Digital input circuit specifications)
Run forward command
[FWD]
Run reverse command
[REV]
Item
Min.
Max.
Operating voltage
(SOURCE)
ON level
22 V
27 V
OFF level
0 V
2 V
Operating voltage
(SINK)
ON level
0V
2V
OFF level
22V
27V
Operating current at ON
(Input voltage is at 27 V)
2.5 mA
5 mA
Allowable leakage current at OFF
0.5 mA
[X1] to [X8],
[FWD],[REV]