iii
Installation
Install the inverter on a base made of metal or other non-flammable material.
Otherwise, a fire could occur.
Do not place flammable object nearby.
Doing so could cause fire.
Do not support the inverter by its front cover during transportation.
Doing so could cause a drop of the inverter and injuries.
Prevent lint, paper fibers, sawdust, dust, metallic chips, or other foreign materials from getting into the
inverter or from accumulating on the heat sink.
When changing the positions of the top and bottom mounting bases, use only the specified screws.
Otherwise, a fire or an accident might result.
Do not install or operate an inverter that is damaged or lacking parts.
Doing so could cause fire, an accident or injuries.
Wiring
If there isn’t zero-phase current (Earth leakage current) detective device, such as a ground-fault relay
in the upstream power supply line, which is to avoid undesirable system shutdown. Install a
residual-current-operated protective device (RCD)/earth leakage circuit breaker (ELCB) individually to
break the individual inverter’s power supply line.
Otherwise, a fire could occur.
When wiring the inverter to the power source, insert a recommended molded case circuit breaker
(MCCB) or residual-current-operated protective device (RCD)/earth leakage circuit breaker (ELCB)
(with overcurrent protection) in the path of each pair of power lines to inverters. Use the recommended
devices within the recommended current capacity.
Use wires in the specified size.
Tighten terminals with specified torque.
Otherwise, a fire could occur.
When there is more than one combination of an inverter and motor, do not use a multicore cable for
the purpose of running their wirings together.
Do not connect a surge killer to the inverter's output (secondary) circuit.
Doing so could cause a fire.
Be sure to ground the inverter's grounding terminals
G.
Otherwise, an electric shock or a fire could occur.
Qualified electricians should carry out wiring.
Be sure to perform wiring after turning the power OFF.
Otherwise, an electric shock could occur.
Be sure to perform wiring after installing the inverter unit.
Otherwise, an electric shock or injuries could occur.