4-3
(2) Stopping operation
When
F 0 2
is other than
1
press
RUN
to start operation or press
STOP
to
stop operation. The direction of rotation is as shown below.
F 0 2
=
0
:Forward rotation with FWD-CM ON, reverse rotation with REV-
CM ON
F 0 2
=
2
:Forward rotation (Inputs at the FWD and REV terminals are
ignored.)
F 0 2
=
3
:Reverse rotation (Inputs at the FWD and REV terminals are
ignored.)
(3) Changing the frequency
When
F 0 1
is at
0
, press the
key to increase the frequency or
press the
key to decrease the frequency. Press and hold the or key and press the
key to increase the frequency change speed.
Note) Do not turn the power off for five seconds after performing a monitor change or
function setting. Otherwise Er1 will be caused.
(4) Function setting method
Description of operation Operation procedure Display result
Initial state
6
0.
0 0
1
Start the program mode.
Press the key.
F 0 0
2
Select a setting or monitoring
Press the or key.
F 0 1
3
Have the data displayed.
Press the key.
1
4
Change the data.
Press the or key.
2
5
Store the data.
Press the key.
F 0 2
6
Exit from the program mode. (Or
select another function.)
Press the key.
(Press the or key.)
6
0.
0 0