EasyManua.ls Logo

Fuji Electric MICREX-SX SPH Series - Connecting a Personal Computer Loader to the RS-232 C Port and RS-485 Port; Loader Network Configuration Using RS-485

Fuji Electric MICREX-SX SPH Series
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-7
3-2 System Configurations
1: 1 / 1: N connection
3-2-5 Connecting a personal computer loader to the RS-232C port and RS-485 port
This configuration connects a D300win personal computer loader to each of RS-232C and RS-485 ports.
RS-485
RS-232C
RS-485 port
Signal conversion
<Mode selection switch: 3>
RS-232C port
Loader
None
Loader
CPU
Power
supply
RS1
For the connection, refer to
3-3 Loader Connecting Cable.
3-2-6 Loader network configuration using RS-485
This configuration connects a D300win personal computer loader to the RS-232C port of RS1 on System 1.
A D300win can communicate with both CPUs of System 1 and System 2.
RS-485
RS-232C
RS-485 port
Signal conversion
<Mode selection switch of System 2: 2>
RS-232C port
Normal
Loader
RS-485 port
Signal conversion
<Mode selection switch of System 1: 5>
RS-232C port
Loader
Yes
General device/loader
When connected to the CPU of System 1, designate, from the
programming loader, the CPU which is in the configuration.
When connected to the CPU of System 2, designate, from the
programming loader, the RS-485 station number of RS1 on System 2.
CPU
Power
supply
RS1
CPU
Power
supply
RS1

Table of Contents

Related product manuals