Parameter List
The following explains each channel parameter.
●
The list also shows the operational range of set values for parameters that are limited.
●
When the PV input lower limit (Pvb), PV input upper limit (PvF), or decimal place position (Pvd) is changed, reconfigure all the initial parameter setting values.
●
When the parameter that has [RESET] on its Remarks column is changed, turn off the power once, and then re-start the controller.
For details, refer to the operation manual (INP-TN5A2400-E) available from our website:
www.fujielectric.com/products/instruments/
Operation control parameter
Parameter
Function
Factory default
setting
Remarks
No Display Name
1
Switchover between auto and manual mode Switchover between auto and manual modes oFF
Note 1
2 Switchover between RUN and standby Switchover the operation mode between RUN and standby oFF
4
Ramp soak control command Changes ramp soak run states oFF Note 2
5
Auto-tuning run command Runs auto-tuning. oFF
6
Alarm output latch release command Cancels the alarm output latch state oFF
7
SV selection Chooses the SV No. used for control LoCL
Note 3
8 PID selection Chooses the PID No. used for control LoCL
9
ALM1 set value Sets the alarm value for ALM1. 2.50%FS10
11
12
ALM2 set value Sets the alarm value for ALM2. 2.50%FS13
14
27
Electric power calculation command
Switches among on/off/hold of electric power calculation.
oFF
28
Key lock Sets the key lock to prevent wrong operation oFF
Note 1: This parameter is not displayed in default setting. If you need to change this parameter, change the setting of “Ch11 dSP” so that it appears.
Note 2: Displays End (when ending) or GS (during guaranty soak).
Note 3:
When changing the SV with the front key, do not change the “Svn” parameter via communication. Otherwise, the changed SV may not be stored correctly.
Note 4:
“SvL” and “Svh” must be set so that SvL < Svh. When you change the values for “SvL” and “Svh”, check SV 1 (“Sv1 Ch2”) through SV 7 (“Sv7 Ch2”).
Note 5: Set the same value as the one for the Normal/Reverse setting (“rEv Ch1”).
Note 6: Do not change this parameter during the ramp soak operation. Be sure to set “PrG” = “oFF” before changing the parameter.
Note 7: Displayed when OUT1 is current or voltage output.
Note 8: Do not change it during calculation.
Note 9: Refer to the Operation Manual for the detail of calculation functions.
CH1 PID (control parameters)
Parameter
Function
Factory default
setting
Remarks
No Display Name
50
Proportional band (%) Sets the proportional band of the PID parameter. 5.0%
51
Integration time
Sets the integration time of the PID parameter.
Setting "0" will turn off integration.
240 (sec)
52
Differential time
Sets the differential band of the PID parameter.
Setting "0" will turn off differentiation.
60.0 (sec)
53
ON/OFF control hysteresis Sets the hysteresis width for the ON/OFF control. 0.25%FS
54
Cooling proportional band coefficient
Sets the proportional band coefficient for cooling.
Setting "0.0" will turn the cooling into an ON/OFF control.
1.0
55
Dead band (%)
Shifts the cooling proportional band from the set value
0.0%
56
Output convergence value (%) Offset value which is added to the MV output value 0
57
Anti-reset windup Sets the range of integration control 100%FS
58
Normal/reverse operations Sets the control action (normal or reverse). RV-- [RESET]
59
SV limit (lower) Sets the lower limit of SV 0.00%FS Note 4
60
SV limit (upper) Sets the upper limit of SV 100.00%FS Note 4
61
OUT1 proportion cycle
Sets the proportion cycle of the control output (OUT1) (contacts, SSR
drive)
30 (relay)
2 (SSR)
1 (current)
63
OUT1 lower limit Sets the lower limit of the control output (OUT1) -5.0%
64
OUT1 upper limit Sets the upper limit of the control output (OUT1) 105.0%
67
Type of output limiter Sets the type of output limiter 0
73
Alpha 6HWVGHJUHHVRIIUHHGRPFRHIILFLHQWĮ 40.0%
74
Beta 6HWVGHJUHHVRIIUHHGRPFRHIILFLHQWȕ 100.0%
CH2 PLT (PID palette parameters)
Parameter
Function
Factory default
setting
Remarks
No Display Name
100
SV1 Sets the SV (set value) 0%FS Note 4
101
Proportional band 1 (%) Sets the proportional band. 5.0%
102
Integration time 1 Sets the integration time. 240 (sec)
103
Differential time 1 Sets the differential time. 60.0 (sec)
104
ON/OFF control hysteresis 1 Sets the hysteresis when using the ON/OFF control. 0.25%FS
105
Cooling proportional band 1 (%)
Sets the cooling proportional band. 1.0
106
Dead band 1 (%) Sets the dead band 0.0%
107
Output convergence value 1 (%) Offset value which is added to the control output 0
108
Anti-reset windup 1 Sets the anti-reset windup 100%FS
109
Normal/reverse 1 Sets the control action (normal or reverse). RV--
[RESET]
Note 5
160
SV 7 Sets the SV (set value) 0%FS Note 4
161
Proportional band 7 (%) Sets the proportional band. 5.0%
162
Integration time 7 Sets the integration time. 240 (sec)
163
Differential time 7 Sets the differential time. 60.0 (sec)
164
ON/OFF control hysteresis 7 Sets the hysteresis when using the ON/OFF control. 0.25%FS
165
Cooling proportional band 7 (%) Sets the cooling proportional band. 1.0
166
Dead band 7 (%) Sets the dead band 0.0%
167
Output convergence value 7 (%) Offset value which is added to the control output 0
168
Anti-reset windup 7 Sets the anti-reset windup 100%FS
169
Normal/reverse 7 Sets the control action (normal or reverse). RV--
[RESET]
Note 5
170
PID switching point 1 Sets the PID switching point for palette 1. 0%FS
176
PID switching point 7 Sets the PID switching point for palette 7. 0%FS
177
Max SV selection number Choosing SV with the user key sets it to the maximum possible number. Sv7
178
Max PID selection number Choosing PID with the user key sets it to the maximum possible number. Pid7
CH 3 PRG (ramp soak parameters)
Parameter
Function
Factory default
setting
Remarks
No Display Name
200
Ramp soak operation pattern (Step No.) Sets which steps to use in the ramp soak operation pattern
14
(uses steps 1 to
64)
Note 6
201
Ramp soak time units Sets the units of the ramp soak time hh.MM
202
Ramp soak 1 seg/SV 1 Sets the SV 0%FS
203
Ramp soak 1 seg ramp time Sets the ramp time. 00:00
204
Ramp soak 1 seg soak time Sets the soak time. 00:00
205
Ramp soak 2 seg/SV 2 Sets the SV 0%FS
206
Ramp soak 2 seg ramp time Sets the ramp time. 00:00
389
Ramp soak 63 seg ramp time Ramp soak 63 seg ramp time 00:00
390
Ramp soak 63 seg soak time Ramp soak 63 seg soak time 00:00
391
Ramp soak 64 seg/SV 64 Ramp soak 64 seg/SV 64 0%FS
392
Ramp soak 64 seg ramp time Ramp soak 64 seg ramp time 00:00
393
Ramp soak 64 seg soak time Ramp soak 64 seg soak time 00:00
394
Ramp soak mode Ramp soak mode 0
395
Guaranty soak ON/OFF Guaranty soak ON/OFF oFF
396
Guaranty soak band (Lower) Guaranty soak band (Lower) 1.25%FS
397
Guaranty soak band (Upper) Guaranty soak band (Upper) 1.25%FS
398
PV start PV start oFF
399
Restore mode Restore mode rES
400
Max pattern selection Max pattern selection 14
401
Min pattern selection Min pattern selection 0
CH 4 MON (monitor parameters)
Parameter
Function
Factory default
setting
Remarks
No Display Name
420
Ramp soak progress Displays the progress of the ramp soak —
421
MV1(%)
Displays the output value of the control output (OUT1)
—
424
Remote SV Shows a remote SV. —
425
Heater current (A)
Shows a heater current value.
(A current value when OUT1 is ON.)
—
427
SSR leak current (A)
Shows a leak current value.
(A current value when OUT1 is OFF.)
—
429
Remaining time on timer 1 Displays the remaining time on timer 1 —
430
Remaining time on timer 2 Displays the remaining time on timer 2 —
436
Current (A) Shows a value measured by CT. —
438
Electric power Shows a calculated value for electric power. —
439
Power Displays the calculated amount of electric power. —
440
Number of opetating times (control relay 1) Displayes the number of times that control relay 1 has operated. —
442
Operating days
Displays the number of days oparated, converted from total operating time.
—
443
Error source Displays the source of an error —
446
Current palette No. Displays the PID palette No. currently selected. —
447
Current pattern No. Displays the pattern No. of the ramp soak currently selected. —
CH5 ALM (monitor parameters)
Parameter
Function
Factory default
setting
Remarks
No Display Name
470
ALM1 alarm type Set the alarm type for ALM1. 0
471
ALM1 hysteresis Sets the hysteresis for alarm output 1 ON/OFF 0.25%FS
472
ALM1 delay Sets the delay before detecting alarm output 1 0
473
ALM1 delay time units Sets the delay time units for alarm output 1 sec
474
ALM1 option
Assigns the optional functions to ALM1
●
Ones digit: alarm output latch
●
Tens digit: error alarm
●
Hundreds digit: inverted output
●
Thousands digit: hold reset
0000
475
ALM2 alarm type Set the alarm type for ALM2. 0
476
ALM2 hysteresis Sets the hysteresis for alarm output 2 ON/OFF 0.25%FS
477
ALM2 delay Sets the delay before detecting alarm output 2 0
478
ALM2 delay time units Sets the delay time units for alarm output 2 sec
479
ALM2 option
Assigns the optional functions to ALM2
●
Ones digit: alarm latch bit mask
●
Tens digit: error alarm bit mask
●
Hundreds digit: inverted output bit mask
●
Thousands digit: hold reset bit mask
0000
511
Electricity alarm Sets the value for electricity alarm. 0
CH 6 SET (setup parameters)
Parameter
Function
Factory default
setting
Remarks
No Display Name
530
PV input type Sets the type of input sensor K1 [RESET]
531
PV input lower limit Sets the lower limit of PV input 0 [RESET]
532
PV input upper limit Sets the upper limit of PV input 400 [RESET]
533
Decimal point position Sets the decimal point position for the PV/SV 0 [RESET]
535
Square-root extractor cut point Sets the cut point for square root calculation. -0.1%
536
PV input shift Sets the amount of shift for PV input 0.00%FS
538
PV input filter Sets the time constant for the PV input filter 5.0 sec
547
OUT1 range Sets the range of the control output 1(OUT1) 4-20 Note 7
549
MV1 during FALT Sets the output value for the control output (MV1) during FALT -5.0%
551
MV1 during Soft Start
Sets the value for the control output (MV1) during soft start
105.0%
553
Soft Start set time Sets the time from startup to the finish of soft start 00:00
554
MV1 during standby
Sets the value for the control output (MV1) during standby
-5.0%
556
Standby mode Sets on/off of the alarm output during standby 0 [RESET]
561
Fixed voltage value Sets the voltage for calculating electric power 100 (100 V)
562
Current value for simple power calculation Sets the current value for simple power calculation 0 (0.0A)
564
Decial point position for electric power Sets the position of decimal point for calculationed power consumption. 1 : 0.1 Note 8
565
Power factor for simple calculation Sets the power factor for simple calculation 1.00
566
Upper limit of relay contact operation
Sets the upper limit on the number of times a relay contact can operate.
If you set it to 0, no alarm will be generated.
100
(100,000 times)
567
Upper limit of operating days
Sets the upper limit on the number of days the device operates. If you
set it to 0, no alarm will be generated.
3650
(3650 days)
Ch 7 SYS (system parameters)
Parameter
Function
Factory default
setting
Remarks
No Display Name
590
USER key Assigns the function to the [USER] key 0
591
USER + UP key $VVLJQVWKHIXQFWLRQWRWKH>86(5@NH\ 1
592
USER + DOWN key Assigns the function to the [USER]+ V key 5
599
OUT1 output type Selects the content to be output from OUT1 1
602
DO1 output type Sets the trigger for DO1 3
603
DO2 output type Sets the trigger for DO2 4
607
LED indicator assignment (OUT1)
Selects the content for OUT1 to indicate. 1
609
LED indicator assignment (Ev1)
Selects the content for EV1 lamp to indicate. 110
610
LED indicator assignment (Ev2)
Selects the content for EV2 lamp to indicate. 111
615
LED indicator assignment (STBY)
Selects the content for STBY lamp to indicate. 12
616
LED indicator assignment (MANU)
Selects the content for MAN lamp to indicate. 13
617
Ramp SV ON/OFF Sets the ramp SV ON/OFF oN
618
Ramp SV-Decline
Sets the slope for a falling SV during ramp SV operations
0.00%FS
619
Ramp SV-Incline
Sets the slope for a rising SV during ramp SV operations
0.00%FS
620
Ramp SV-slope time unit Sets the unit of time for the slope during ramp SV operations hoUr
621
Ramp SV - display mode
Displays the SV during ramp operations or the SV goal value on the SV
display
rMP
622
Control method Selects the control method. Pid
626
Start mode Sets the operation mode during startup AUTO
627
Control operation cycle Sets the control operation cycle. 0.1S
628
PID pallette switching method Sets the method for switching among PID pallette. 0
Ch 12 CFG (configuration parameters)
Parameter
Function
Factory default
setting
Remarks
No Display Name
940
Operation timeout (return to PV/SV display)
Sets the time until the display returns to PV/SV screen from setting screen.
60S
942
Blinking SV during Soft Start Sets whether or not to blink SV during Soft Start. ON
943
Blinking PV/SV at ALM Sets whether or not to blink PV/SV when alarm becomes ON. 0
944
Display timeout Sets the time until the display automatically turns off. oFF
945
PV/SV Display off Sets ON/OFF of PV and SV display 0
946
Blinking PV at input error Sets whether or not to blink PV at an input error 0
947
Brightness Sets the brightness of LED backlight 3 3 is the brightest
948
Control at burnout
Sets whether to continue or to stop control when the device detects a
burnout of PV input
oFF
950
Model code Shows model code
P
951
X
952
F
962
963
Reset
Resets the controller
oFF
965
Software version
Shows the software version
—
966
967
968
Ch 13 PASS (password parameters)
Parameter
Function
Factory default
setting
Remarks
No Display Name
990
Password1 setup Sets password 1. 0000
991
Password2 setup Sets password 2. 0000
992
Password3 setup Sets password 3. 0000
Ch 8 MATH (calculation parameters)
Parameter
Function
Factory default
setting
Remarks
No Display Name
650
Simple calculation ON/OFF Sets ON/OFF of simple calculation oFF Note 9
Ch 11 DSP (parameter mask)
Parameter
Function
Factory default
setting
Remarks
No Display Name
1 — Parameter mask Sets the parameters to be displayed/not displayed. — Values differ depending on the model.