&+6(7VHWXSSDUDPHWHUV
3DUDPHWHU
)XQFWLRQ 6HWWLQJUDQJH ,QLWLDOYDOXH 5HPDUNV
ʋ 'LVSOD\ 1DPH
530
PV input type Sets the type of input sensor JPT1: 0.0 to 150.0°C
JPT2: 0.0 to 300.0°C
JPT3: 0.0 to 500.0°C
JPT4: 0.0 to 600.0°C
JPT5: -50.0 to 100.0°C
JPT6: -100.0 to 200.0°C
JPT7: -199.9 to 600.0°C
PT1: 0.0 to 150.0°C
PT2: 0.0 to 300.0°C
PT3: 0.0 to 500.0°C
PT4: 0.0 to 600.0°C
PT5: -50.0 to 100.0°C
PT6: -100.0 to 200.0°C
PT7: -199.9 to 600.0°C
PT8: -200 to 850°C
J1: 0.0 to 400.0°C
J2: -20.0 to 400.0°C
J3: 0.0 to 800.0°C
J4: -100 to 1000°C
K1: 0 to 400°C
K2: -20.0 to 500.0°C
K3: 0.0 to 800.0°C
K4: -200 to 1300°C
R: 0 to 1700°C
B: 0 to 1800°C
S: 0 to 1700°C
T1: -199.9 to 200.0°C
PT2: -199.9 to 400.0°C
E1: 0.0 to 740.0°C
E2: -150.0 to 740.0°C
E3: -200 to 740°C
/WR&
U1: -199.9 to 400.0°C
U2: -200 to 400°C
N: -200 to 1300°C
W: 0 to 2300°C
3/WR&
0-5 V: 0 to 5 V
1-5 V: 1 to 5 V
0-10: 0 to 10 V
2-10: 2 to 10 V
MV: 0 to 100 mV
0-20: 0 to 20 mA
4-20: 4 to 20 mA
K1 [RESET]
Refer to section 10 for the detail.
531
39LQSXWORZHUOLPLW 6HWVWKHORZHUOLPLWRI39LQSXW -1999 to 9999 0 [RESET]
532
PV input upper limit Sets the upper limit of PV input -1999 to 9999 400 [RESET]
533
Decimal point position Sets the decimal point position for the PV/SV 0: No digit after decimal point
1: 1 digit after decimal point
2: 2 digit after decimal point
3: 3 digit after decimal point
0 [RESET]
535
6TXDUHURRWH[WUDFWRUFXWSRLQW Sets the cut point for square root calculation. -0.1 to 105.0(%) -0.1%
536 PV input shift Sets the amount of shift for PV input -10 to 10%FS 0.00%FS
538 39LQSXW¿OWHU 6HWVWKHWLPHFRQVWDQWIRUWKH39LQSXW¿OWHU 0.0 to 120.0 sec 5.0 sec
543
5HPRWH69]HURDGMXVWPHQW $GMXVWVWKH]HURVLGHRIUHPRWH69 -50 to 50%FS 0.00%FS
544
5HPRWH69VSDQDGMXVWPHQW $GMXVWVWKHVSDQVLGHRIUHPRWH69 -50 to 50%FS 0.00%FS
545 Remote SV input range Sets the range for remote SV input. 0-5v: 0 to 5 V
1-5v: 1 to 5 V
0-10: 0 to 10 V
2-10: 2 to 10 V
1-5V
546 5HPRWH69LQSXW¿OWHU 6HWVWKHWLPHFRQVWDQWIRUWKH569LQSXW¿OWHU 0.0 to 120.0 s 0.0 s
547
OUT1 range Sets the range of the control output 1(OUT1) 0-5v: 0 to 5 V
1-5v: 1 to 5 V
0-10: 0 to 10 V
2-10: 2 to 10 V
0-20: 0 to 20 mA
4-20: 4 to 20 mA
0-10 (voltage)
4-20 (current)
'LVSOD\HGZKHQ287LVFXUUHQWRUYROWDJHRXWSXW
548 OUT2 range Sets the range of the control output 2(OUT2) 0-5v: 0 to 5 V
1-5v: 1 to 5 V
0-10: 0 to 10 V
2-10: 2 to 10 V
0-20: 0 to 20 mA
4-20: 4 to 20 mA
0-10 (voltage)
4-20 (current)
'LVSOD\HGZKHQ287LVFXUUHQWRUYROWDJHRXWSXW
549
09GXULQJ)$/7 Sets the output value for the control output (MV1) during
)$/7
-5.0 to 105.0% -5.0%
550 09GXULQJ)$/7 Sets the output value for the control output (MV2) during
)$/7
-5.0 to 105.0% -5.0%
551 MV1 during Soft Start Sets the value for the control output (MV1) during soft start -5.0 to 105.0% 105.0%
553 Soft Start set time 6HWVWKHWLPHIURPVWDUWXSWRWKH¿QLVKRIVRIWVWDUW 00:00 to 99:59 (hour:min) 00:00 Be sure to set 0.00 during dual control.
554 MV1 during standby Sets the value for the control output (MV1) during standby -5.0 to 105.0% -5.0%
555 MV2 during standby Sets the value for the control output (MV2) during standby -5.0 to 105.0% -5.0%
556 Standby mode Sets on/off of the alarm output during standby $/0 2))$2 21
$/0 21$2 21
$/0 2))$2 2))
$/0 21$2 2))
0 [RESET]
557
AO 6HOHFWVZKDWWRWUDQVIHUWRWKHDQDORJRXWSXW PV
SV
MV
DV
PFb: Not for use.
PV
558
$2ORZHUVFDOLQJ 6HWVWKH$2ORZHUVFDOLQJ -100.0 to 100.0% 0.0%
559
AO upper scaling Sets the AO upper scaling -100.0 to 100.0% 100.0%
561
)L[HGYROWDJHYDOXH 6HWVWKHYROWDJHIRUFDOFXODWLQJHOHFWULFSRZHU 1 to 500V 100 (100 V)
562 &XUUHQWYDOXHIRUVLPSOHSRZHU
calculation
6HWVWKHFXUUHQWYDOXHIRUVLPSOHSRZHUFDOFXODWLRQ 0.0 to 100.0A 0 (0.0A)
564
'HFLDOSRLQWSRVLWLRQIRUHOHFWULFSRZHU 6HWVWKHSRVLWLRQRIGHFLPDOSRLQWIRUFDOFXODWLRQHGSRZHU
consumption.
0 : 0
1 : 0.1
2 : 0.01
3 : 0.001
1 : 0.1 Do not change it during calculation.
565
3RZHUIDFWRUIRUVLPSOHFDOFXODWLRQ 6HWVWKHSRZHUIDFWRUIRUVLPSOHFDOFXODWLRQ 0.00 to 1.00 1.00
566 Upper limit of relay contact operation Sets the upper limit on the number of times a relay contact
FDQRSHUDWH,I\RXVHWLWWRQRDODUPZLOOEHJHQHUDWHG
0 to 9999 100
(100,000 times)
567 Upper limit of operating days Sets the upper limit on the number of days the device
RSHUDWHV,I\RXVHWLWWRQRDODUPZLOOEHJHQHUDWHG
0 to 5000 3650 (3650 days)
- 11 -