&K6<6V\VWHPSDUDPHWHUV
3DUDPHWHU
)XQFWLRQ 6HWWLQJUDQJH ,QLWLDOYDOXH 5HPDUNV
ʋ 'LVSOD\ 1DPH
590
USER key Assigns the function to the [USER] key 0 to 29 0 Refer to section 12 for the detail.
591 USER + UP key $VVLJQVWKHIXQFWLRQWRWKH>86(5@೸NH\ 0 to 29 1
592
USER + DOWN key Assigns the function to the [USER]+ V key 0 to 29 5
593
DI-1 function select Allocates a function to DI-1. 0-48 0 Refer to Section 14 for the detail.
594
DI-2 function select Allocates a function to DI-2. 0-48 0
595
DI-3 function select Allocates a function to DI-3. 0-48 0
599 OUT1 output type Selects the content to be output from OUT1 0 to 427 1 Refer to section 13 for the detail.
600 OUT2 output type Selects the content to be output from OUT2 0 to 427 2
601 DO1 output type Sets the trigger for DO1 0 to 427 3
602 DO2 output type Sets the trigger for DO2 0 to 427 4
603
DO3 output type Selects the content to be output from DO3. 0 to 427 5
607
/('LQGLFDWRUDVVLJQPHQW287 Selects the content for OUT1 to indicate. 0 to 427 1
608 /('LQGLFDWRUDVVLJQPHQW287 Selects the content for OUT2 to indicate. 0 to 427 2
609
/('LQGLFDWRUDVVLJQPHQW(Y Selects the content for EV1 lamp to indicate. 0 to 427 110
610
/('LQGLFDWRUDVVLJQPHQW(Y Selects the content for EV2 lamp to indicate. 0 to 427 111
611 /('LQGLFDWRUDVVLJQPHQW(Y Selects the content for EV3 lamp to indicate. 0 to 427 112
615 /('LQGLFDWRUDVVLJQPHQW67%< 6HOHFWVWKHFRQWHQWIRU67%<ODPSWRLQGLFDWH 0 to 427 12
616
/('LQGLFDWRUDVVLJQPHQW0$18 Selects the content for MAN lamp to indicate. 0 to 427 13
617
Ramp SV ON/OFF Sets the ramp SV ON/OFF oFF
oN
oN
618
Ramp SV-Decline Sets the slope for a falling SV during ramp SV operations 0 to 100%FS 0.00%FS
619
Ramp SV-Incline Sets the slope for a rising SV during ramp SV operations 0 to 100%FS 0.00%FS
620 Ramp SV-slope time unit Sets the unit of time for the slope during ramp SV operations hoUr: slope temperature/hour
Min: slope temperature/min
hoUr
621 Ramp SV - display mode Displays the SV during ramp operations or the SV goal value
on the SV display
rMP: ramping SV
TrG: target SV
rMP
622
Control method Selects the control method. oNoF: ON/OFF control
Pid: PID control
)8=\)X]\FRQWURO
6(/)6HOIWXQLQJFRQWURO
Pid2: PID2 control
2FRE: 2-degrees-of-freedom PID
Pid
626
Start mode Sets the operation mode during startup AUTo: starts in AUTO mode
MAn: starts in manual mode
REM: starts in remote mode
67E<VWDUWVLQVWDQGE\PRGH
AUTO
627 Control operation cycle Sets the control operation cycle. 0.1 to 0.9S, 1 to 99S 0.1S
628
3,'SDOOHWWHVZLWFKLQJPHWKRG 6HWVWKHPHWKRGIRUVZLWFKLQJDPRQJ3,'SDOOHWWH VHOHFWHG3,'ʋ
VHOHFWHG69ʋ
2: PV
0
&K0$7+FDOFXODWLRQSDUDPHWHUV
3DUDPHWHU
)XQFWLRQ 6HWWLQJUDQJH ,QLWLDOYDOXH 5HPDUNV
ʋ 'LVSOD\ 1DPH
650 Simple calculation ON/OFF Sets ON/OFF of simple calculation oFF
oN
oFF Note 1)
Note 1: Refer to the operation manual for the detail of calculation functions.
&K&20FRPPXQLFDWLRQSDUDPHWHUV
3DUDPHWHU
)XQFWLRQ 6HWWLQJUDQJH ,QLWLDOYDOXH 5HPDUNV
ʋ 'LVSOD\ 1DPH
760
Communication type Selects a type of communication. 0: MODBUS RTU
1: Cooperative operation
2: Programless communication
0 [RESET]
Note 1)
761
Station No. Sets the station number. 0 to 255 (0: unresponsive communication) 1 [RESET]
762 RS-485 baud rate Sets the baud rate 96: 9600 bps
192: 19200 bps
384: 38400 bps
115K: 115 Kbps
96 [RESET]
763
RS-485 parity Sets the parity check none
odd
even
odd [RESET]
764
RS-485 response interval Widen the time interval of receiving response. (Set value × 20
ms)
0 to 100 1 (20 ms) [RESET]
767
Communication permissions 6HWVZKHWKHURUQRWRYHUZULWLQJLVSRVVLEOHIURPWKHPDVWHU
side (PC, etc.)
r: Read only
U:5HDGRYHUZULWHSHUPLWWHG
rW [RESET]
769
MODBUS user address setting 1 Sets the MODBUS user address 30001 [RESET]
800 MODBUS user address setting 32 30001 [RESET]
842 $XWR)L[ 6HWVWKHDXWRZULWHIXQFWLRQIRUFRPPXQLFDWLRQ oN/oFF oN Note 2)
Note 1: Refer to the communication instruction manual (MODBUS) for the detail of communication functions.
1RWH<RXFDQQRWVHWRUFKDQJHWKLVSDUDPHWHUE\XVLQJWKHORDGHUVRIWZDUH
&K3)%3)%SDUDPHWHUV
3DUDPHWHU
)XQFWLRQ 6HWWLQJUDQJH ,QLWLDOYDOXH 5HPDUNV
ʋ 'LVSOD\ 1DPH
870 PFB dead band Sets the dead band for PFB. 0.0% to 100.0% 5.0%
871 Valve stroke time 6HWVWKHIXOOVWURNHWLPHIRUWKHPRWRUL]HGYDOYH 5 s to 180 s 30 s
&K'63SDUDPHWHUPDVN
3DUDPHWHU
)XQFWLRQ 6HWWLQJUDQJH ,QLWLDOYDOXH 5HPDUNV
ʋ 'LVSOD\ 1DPH
1 Parameter mask Sets the parameters to be displayed/not displayed. oFF/diSP Values differ
depending on the
model.
- 12 -