STRUCTURE
_______________________________________________________
Mounting method Panel flush mounting or surface mounting
Surface mounting: PXZ-4 type only
_______________________________________________________
External terminal PXZ-4 type: 8-pin or 11-pin socket
Other types: screw terminal (M3.5 screw)
_______________________________________________________
Enclosure Black ABS plastic
_______________________________________________________
Dimensions PXZ-4 48 x 48 x 85.7mm (1/16 DIN)
PXZ-5 52.5 x 100.5 x 95.8mm (1/8 DIN)
PXZ-7 76.5 x 76.5 x 95.8mm (72 mm)
PXZ-9 100.5 x 100.5 x 95.8mm (1/4 DIN)
_______________________________________________________
Weight PXZ-4 approx. 150g
PXZ-5 approx. 300g
PXZ-7 approx. 300g
PXZ-9 approx. 400g
_______________________________________________________
Protective structure Front panel water-proof structure;
NEMA 4X (equivalent to IEC standards IP66)
Rear case: IEC IP20
_______________________________________________________
DELIVERY
_______________________________________________________
PXZ-4 type: controller, panel mounting bracket, socket (when specified),
water proof gasket, 250 precision resistor (when required), instruction
manual. Other types: controller, panel mounting bracket, water-proof gasket,
250 precision resistor (when required), instruction manual.
_______________________________________________________
4
GENERAL SPECIFICATIONS
_______________________________________________________
Rated voltage 85-264V AC or 24V AC/DC
_______________________________________________________
Power consumption 10VA or less (100V AC)
15VA or less (240V AC)
_______________________________________________________
Insulation resistance 50M or more (500V DC)
_______________________________________________________
Withstand voltage Power source-Earth: 1500V AC, 1 min
Power source-input terminal: 1500V AC, 1 min
Earth-relay output: 1500V AC, 1 min
Earth-Alarm output: 1500V AC, 1 min
Between other terminals: 500V AC, 1 min
_______________________________________________________
Input impedance Thermocouple: 1M or more
Voltage: 450K or more
Current: 250 (external resistor)
_______________________________________________________
Allowable signal Thermocouple: 100 or less
source resistance Voltage: 1Kor less
_______________________________________________________
Allowable wiring RTD: 10 or less per wire
resistance
_______________________________________________________
Reference junction ± 1 °C (at 23°C)
compensation accuracy
_______________________________________________________
Process variable offset ±10% FS
_______________________________________________________
Setpoint variable offset ± 50% FS
_______________________________________________________
Input filter 0-900.0 sec, setting in 0.1 sec steps
(primary lagging filter)
_______________________________________________________
Noise rejection ratio Normal mode noise (50/60Hz): 50dB or more
Common mode noise (50/60Hz): 140dB or more
_______________________________________________________
POWER FAILURE PROTECTION
_______________________________________________________
Memory protection: Non-volatile memory. Parameter values
remain unchanged with disruption of power.
Ramp/soak function has to be re-initiated.
_______________________________________________________
SELF-CHECK
_______________________________________________________
Method: Watchdog timer monitors program error.
_______________________________________________________
OPERATION AND STORAGE CONDITIONS
_______________________________________________________
Operating temperature -10 to 50°C (14 to 122°F)
_______________________________________________________
Operating humidity 90% RH or less (non-condensing)
_______________________________________________________
Storage temperature -20 to 60°C (-4 to 140°F)
_______________________________________________________
Installation category II
_______________________________________________________
Pollution degree 2
_______________________________________________________
OTHER FUNCTIONS
_______________________________________________________
Parameter mask function Parameter display is disabled by software
_______________________________________________________
Ramp soak function 4-ramp/4-soak
_______________________________________________________
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com