— 19 —
5 Useful usage of this equipment
Select the sensor you use from those in Table 1, and set it in the
parameter P-n2.
(Example) For T thermo-couple, set P-n2 to "7".
(Note) Changing between resistance bulb and thermo-couple
is allowed, though that between 1 to 5VDC (4 to 20mA DC)
and thermo-couple/resistance bulb is not allowed.
Standard range to each sensor is shown in Table 2. Select the
temperature range suitable for the equipment you use, set
lower/upper limit values to P-SL/P-SU respectively.
(Example) Temperature range 0 to 800 [°C] set P-SL and P-SU to
0 and 800 respectively.
(Note) Standard range is recommended to set though other setting
is available.
(Note) No standard range is given if 1 to 5VDC(4 to 20mA DC) are
input.
Any upper/lower limits can be set (-1999 to 9999, and lower
limit< upper limit)
w Is setting of input temperature range suitable for the
sensor you use?
Setting
the input
* Skip this procedure
if specified when
you order.
1
q Is the input sensor type same as what you use ?
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com