38
[Description]
• This function is used to calibrate
input by user.
• Using zero input or span input, er-
ror is set in the input range.
• User calibration function is indepen-
dent of adjustment of the controller.
By setting 0 in this parameter, it can
easily be set back to the state prior
to delivery from the factory.
• It is used to set the same reading
between controllers or between con-
troller and recorder.
Example)
When the input range is 0 to 400°C,
the reading at 0°C input is -1°C and
that at 400°C is 402°C.
In this case, when ADJO param-
eter is set to 1 and ADJS to -2, the
reading at 0°C input becomes 0°C
and that at 400°C input becomes
400°C.
When both ADJO and ADJS are
set to 0, the controller is set in the
calibrated state prior to delivery
from the factory.
Example) Set zero adjustment to +1°C
Key operation Description
Press the SEL key for 3 seconds,
and P-n1 is displayed.
Press the SEL key repeatedly until
ADJO is displayed.
Press the or key to display
1.
Press the DATA key. Current data
is displayed.
Press the SV key when you need to
display the operation status display.
After pressing the ENT key, the data
is registered.
Display
SEL
SEL
SV
DATA
ENT
User’s adjust zero adjustment (Setting range: -50 to 50%FS)
User’s adjust span adjustment (Setting range: -50 to 50%FS)