When function setting is "Operation/Stop" mode 2
In the case of "Edge" input
Mode Function setting External input Input signal Command
0 46-03
Input of indoor unit
CN14
Off → On Operation
On → Off
Stop (R.C.
disabled)
60-00 CN15
Off → On Operation
On → Off
Stop (R.C.
disabled)
On
CN15
Off
Operation
Indoor unit
Stop
(R.C. disabled)
Remote contoller
On OnOff
Forced thermostat off function
Mode Function setting External input Input signal Command
0
9
10
60-00
60-09
60-10
Input of indoor unit CN15
Off → On
Thermostat
off
On → Off
Normal
operation
On
Off
On
Off
Compressor
Room temp.
Set temp.
Input
Example of individual connection
Forced thermostat off is one of the function to save energy. For example, case of using ventilator
at condition with outdoor temperature is lower than indoor temperature, indoor unit of air condition-
er stop based upon receiving signal from external controller. (Cooling only)
76°F
80°F
74°F
84°F
68°F
Away
Custom
Auto
Auto
Cool
Heat
Office
Set Temp.
Mode
MenuStatus
Vacation
Fan
Fri 10:00AM
Room Temp.
Cool
Heat
76°F
80°F
74°F
84°F
68°F
Away
Custom
Auto
Auto
Cool
Heat
Office
Set Temp.
Mode
MenuStatus
Vacation
Fan
Fri 10:00AM
Room Temp.
Cool
Heat
28˚C
Cooling operation
(Thermostat on)
Fan stop
(Thermostat off)
Indoor
temperature
Outdoor
temperature
Outdoor
temperature
Direct digital
controller
Thermistor
Thermistor
Ventilator
Indoor
temperature
31˚C 28˚C 24˚C
- 19 -
8-4. Details of function 8. External input and output
FLOOR TYPE
AGYG09-14KVCA
FLOOR TYPE
AGYG09-14KVCA