6-2. Model: AOYG14KVCA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 0.950 0.946
10 0.976 0.958 0.954
7.5 0.984 0.980 0.962 0.958
5 0.992 0.988 0.984 0.966 0.962
0 1.000 0.996 0.992 0.974 0.969
Indoor unit is lower than
outdoor unit *2
-5 1.000 0.996 0.992 0.974 0.969
-7.5 0.996 0.992 0.974 0.969
-10 0.992 0.974 0.969
-15 0.974 0.969
HEATING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 0.853 0.824
10 0.943 0.853 0.824
7.5 0.982 0.943 0.853 0.824
5 1.000 0.982 0.943 0.853 0.824
0 1.000 0.982 0.943 0.853 0.824
Indoor unit is lower than
outdoor unit *2
-5 0.995 0.977 0.938 0.848 0.820
-7.5 0.975 0.936 0.846 0.818
-10 0.933 0.844 0.816
-15 0.785 0.758
- 48 -
6-2. Model: AOYG14KVCA 6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYG09-14KVCA
OUTDOOR UNIT
AOYG09-14KVCA