6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit *
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H H
6-1. Models: AOYG09KVCA and AOYG12KVCA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 — — — 0.915 0.905
10 — — 0.955 0.922 0.912
7.5 — 0.974 0.959 0.926 0.916
5 0.992 0.978 0.963 0.930 0.920
0 1.000 0.986 0.971 0.937 0.927
Indoor unit is lower than
outdoor unit *2
-5 1.000 0.986 0.971 0.937 0.927
-7.5 — 0.986 0.971 0.937 0.927
-10 — — 0.971 0.937 0.927
-15 — — — 0.937 0.927
HEATING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 — — — 0.863 0.846
10 — — 0.944 0.863 0.846
7.5 — 0.978 0.944 0.863 0.846
5 1.000 0.978 0.944 0.863 0.846
0 1.000 0.978 0.944 0.863 0.846
Indoor unit is lower than
outdoor unit *2
-5 0.995 0.973 0.939 0.858 0.842
-7.5 — 0.971 0.937 0.856 0.840
-10 — — 0.934 0.854 0.838
-15 — — — 0.794 0.778
- 47 -
6-1. Models: AOYG09KVCA and AOYG12KVCA 6. Capacity compensation rate for pipe length and height difference