Table 4.11-9 DIP SW4-1, 4-2 setting
Table 4.11-12 DIP SW6-1, 6-2 setting
SW6-1 SW6-2 Pipe Length (m) Remarks
OFF OFF 40 < Pipe Length
<
=
80
(Factory setting)
OFF ON Pipe Length
<
=
40
ON OFF
80 < Pipe Length < 120
ON ON
120 < Pipe Length
<
=
150
4. SW4 Setting
SW4-1, 4-2 (Number of connectable outdoor units)
This DIP switch setting sets the number of outdoor units.
There is no need to make this setting on the slave unit.
SW4-4 Error reset (Setting for master and slave unit)
In the event of compressor failure etc., error information is
stored in PCB.
After repairing the parts and turn ON the power, set the DIP-
SW for reset the error.
(Note : without above setting, error information cant be re-
leased and continue to Error display.)
5. SW5 Setting
SW5-1, 5-2 (Cooling ability shift switch setting)
Set them as necessary.
There is no need to make this setting on the slave unit.
SW5-3, 5-4 (Heating ability shift switch setting)
Set them as necessary.
There is no need to make this setting on the slave unit.
6. SW6 Setting
SW6-1, 6-2 (Pipe Length)
This SW setting can be used to provide operation to supple-
ment the loss created by the pipe length.
There is no need to make this setting on the slave unit.
7. SW7 Setting
SW7-1 (Model Type)
SW7-3 (Indoor unit small capacity setting)
If the total capacity of the connected indoor units is less than
90% of the outdoor unit capacity, set this switch to ON.
There is no need to make this setting on the slave unit.
Table 4.11-10 SW5-1, 5-2 setting
SW5-1 SW5-2 Ability Shift
OFF OFF Normal (Factory setting)
OFF ON Save energy mode
ON OFF High power mode 1
ON ON High power mode 2
Table 4.11-11 SW5-3, 5-4 setting
SW5-3 SW5-4 Ability Shift
OFF OFF Normal (Factory setting)
OFF ON Save energy mode
ON OFF High power mode 1
ON ON High power mode 2
Table 4.11-13 DIP SW7-1 setting
SW7-1 Model Type Remarks
OFF Heat Pump Factory setting
ON Cooling Only
SW4-1 SW4-2 Remarks
OFF OFF 0 (Factory setting) Master unit only
OFF ON 1
ON OFF 2
ON ON Forbidden
Number of
connectable
outdoor units
1 slave unit
connected
2 slave units
connected
Table 4.11-14 DIP SW7-3 setting
OFF 90% or more Factory setting
ON less than 90%
SW7-3
Indoor unit installation
capacity
Remarks
SW4-4 Error reset
OFFON
Error reset
ONOFF