EasyManua.ls Logo

Fujitsu AJ**A72LBTF - ERROR DISPLAY; NORMAL OPERATION MODE

Fujitsu AJ**A72LBTF
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
En-32
OFF
ON
LED 1
LED 2-6
OFF
ON
0.5 sec
2 sec
0.5 sec
LED6 LED5 LED4
LED3 LED2 LED1
LED 1Display
Idling (stopped)
Cooling operation
Heating operation
Compressor 1 output
Compressor 2 output
Compressor 3 output
Compressors 1, 2 output
Compressors 1, 3 output
Compressors 2, 3 output
Compressors 1, 2, 3 output
Equalizing pressure
Oil recovery operation
Defrosting operation
Test operation
Oil level balance operation
Pump down completed
Discharge temperature protection stopped
High pressure protection stopped
Low pressure protection stopped
LED 2
(1)
(2)
(2)
LED 3
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(2)
LED 4
(2)
LED 5
(1)
(2)
(3)
(4)
(2)
LED 6
(2)
(1)
(2)
(3)
Fig. 7.1-1 Details of the LED lamps
* Refer to Fig. 4.11-1 for positions on the LED circuit board.
: Lighted continuously
Display Method
: 0.5 sec ON/0.5 sec OFF flashing
( ) : Flashing times
{
Operation display
7. ERROR DISPLAY
Operation can be checked by the lighting and flashing of the LED lamps.
Perform judgment in accordance with the following.
7.1. NORMAL OPERATION MODE
9374241033_IM_en_p18-36.p65 26/8/2008, 18:2432