2) Static pressure
Select the appropriate static pressure according to the installation conditions.
Function number Setting value Setting description Factory setting
26
03 0.12 inWG (30 Pa)
04 0.16 inWG (40 Pa)
05 0.20 inWG (50 Pa)
06 0.24 inWG (60 Pa)
07 0.28 inWG (70 Pa)
08 0.32 inWG (80 Pa)
09 0.36 inWG (90 Pa)
10 0.40 inWG (100 Pa)
11 0.44 inWG (110 Pa)
12 0.48 inWG (120 Pa)
13 0.52 inWG (130 Pa)
14 0.56 inWG (140 Pa)
15 0.60 inWG (150 Pa)
16 0.64 inWG (160 Pa)
17 0.68 inWG (170 Pa)
18 0.72 inWG (180 Pa)
19 0.76 inWG (190 Pa)
20 0.80 inWG (200 Pa)
31
Standard
12/18/24 model: 0.18 inWG (45 Pa)
30/36/42 model: 0.23 inWG (57 Pa)
48 model: 0.28 inWG (70 Pa)
32 Automatic airflow adjustment
NOTE: Range of static pressure is different by model.
Model name Range of static pressure
12//18/24/30/36 model 0.12 to 0.8 inWG (30 to 200 Pa)
42/48 model 0.12 to 0.72 inWG (30 to 180 Pa)
- 86 -
9-2. Function settings by using remote controller 9. Function settings
DUCT TYPE
ARU12-48RGLX
DUCT TYPE
ARU12-48RGLX

Table of Contents

Other manuals for Fujitsu AOU24RGLX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOU24RGLX and is the answer not in the manual?

Fujitsu AOU24RGLX Specifications

General IconGeneral
BrandFujitsu
ModelAOU24RGLX
CategoryAir Conditioner
LanguageEnglish

Related product manuals