3) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufactur-
er’s recommended value).
Function number Setting value Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00 Standard setting
01 No correction 0.0 °F (0.0 °C)
02 -1 °F (-0.5 °C)
More cooling
Less heating
03 -2 °F (-1.0 °C)
04 -3 °F (-1.5 °C)
05 -4 °F (-2.0 °C)
06 -5 °F (-2.5 °C)
07 -6 °F (-3.0 °C)
08 -7 °F (-3.5 °C)
09 -8 °F (-4.0 °C)
10 +1 °F (+0.5 °C)
Less cooling
More heating
11 +2 °F (+1.0 °C)
12 +3 °F (+1.5 °C)
13 +4 °F (+2.0 °C)
14 +5 °F (+2.5 °C)
15 +6 °F (+3.0 °C)
16 +7 °F (+3.5 °C)
17 +8 °F (+4.0 °C)
4) Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor may be
required. Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both “01”.
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
Function number Setting value Setting description
Factory
setting
35
(For cooling)
36
(For heating)
00 Standard setting
01 No correction 0.0 °F (0.0 °C)
02 -1 °F (-0.5 °C)
More cooling
Less heating
03 -2 °F (-1.0 °C)
04 -3 °F (-1.5 °C)
05 -4 °F (-2.0 °C)
06 -5 °F (-2.5 °C)
07 -6 °F (-3.0 °C)
08 -7 °F (-3.5 °C)
09 -8 °F (-4.0 °C)
10 +1 °F (+0.5 °C)
Less cooling
More heating
11 +2 °F (+1.0 °C)
12 +3 °F (+1.5 °C)
13 +4 °F (+2.0 °C)
14 +5 °F (+2.5 °C)
15 +6 °F (+3.0 °C)
16 +7 °F (+3.5 °C)
17 +8 °F (+4.0 °C)
- 87 -
9-2. Function settings by using remote controller 9. Function settings
DUCT TYPE
ARU12-48RGLX
DUCT TYPE
ARU12-48RGLX

Table of Contents

Other manuals for Fujitsu AOU24RGLX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOU24RGLX and is the answer not in the manual?

Fujitsu AOU24RGLX Specifications

General IconGeneral
BrandFujitsu
ModelAOU24RGLX
CategoryAir Conditioner
LanguageEnglish

Related product manuals