Compressor
ON
OFF
Indoor fan
Setting air flow
OFF
10 30 60 180 60 180 60 10 30
(sec)
S-Lo
480rpm
( Fig.9 : Indoor fan control )
9. FAN CONTROL FOR ENERGY SAVING
When the air flow setting except AUTO mode, the indoor fan motor will run as shown in Fig. 9.
( Factory setting)
Setting Description Function Number Setting Value
Disable
Enable
Remote controller
49
02
00
01
00 : When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01 : When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.
02 : Enable or disable this function by remote controller setting.
Set to “00”or “01”when connecting a remote controller that cannot set
the Fan control for energy saving function or connecting a network converter.
To confirm if the remote controller has this setting,
refer to the operating manual of each remote controller.
Switch the airflow [AUTO] at cooling mode, addition, in the case of Energy saving setting "ON"
and the indoor fan motor will run as shown in Fig. 8.
8. MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)
( Fig. 8 : Indoor Fan Control )
Compressor
ON
OFF
Indoor fan
Setting air flow
Indoor fan
(as shown in Table 5)
S-Lo
OFF
10 30 60 180 60 180 60 10 30
(SEC)
( Table 6 : Indoor fan speed )
X zone J zone Y zone
ASU30RLE 780rpm 680rpm 540rpm 780rpm
Dry
Cooling
01-06