1-5. INDOOR FAN CONTROL
1. Fan speed
( Table 5 : Indoor fan speed )
Operation mode Air flow mode Speed (rpm)
Cooling /
Heating
Dry X : 780
J : 680
Hi
Powerful
Powerful
Me+
Me
Lo
Quiet
Cool air prevention
Hi
Me
Lo
Quiet
S-Lo
1370
1520
1150
1260
950
780
600
1370
1520
950
1150
780
540
2. FAN OPERATION
The airflow can be switched in 5 steps such as Auto, Quiet, Low, Med, High, while the indoor fan only runs.
4. DRY OPERATION
The airflow can be switched in 5 steps such as Auto, Quiet, Low, Med, High, while the indoor fan only runs.
3. COOLING OPERATION
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature, as shown in Fig.7.
On the other hand, if switched in [High] [Quiet], the indoor motor will run at a constant airflow of [Cool]
operation modes Quiet, Low, Med, High, as shown in Table 5.
( Fig.5 : Airflow change - over ( Cooling : Auto ) )
When the room
temperature rises
When the room
temperature drops
Tr : Room temperature
Ts : Setting temperature
Tr-Ts > 4°F
(2°C)
(2°C)
=
2°F
(1°C)
> Tr-Ts
4°F > Tr-Ts > 2°F
(1°C)
=
Tr-Ts > 5°F
(2.5°C)
=
3°F
(1.5°C)
> Tr-Ts
5°F
(2.5°C)
> Tr-Ts > 3°F
(1.5°C)
=
Hi
Me
Lo
01-04