3. ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger
temperature sensor detects the temperature lower than Temperature .
Then, the anti-freezing control is released when it becomes higher than Temperature .
( Table 31 : Anti-freezing protection operation / Release temperature )
Outdoor temperature
Over than 10°C
*1
or 12°C *2
Less than 10°C *1
or 12°C *2
*1. When the temperature rises.
*2. When the temperature drops.
39.2°F (4°C)
44.6°F (7°C)
55.4°F (13°C)
Temperature Temperature
154.4°F (68°C)
145.4°F (63°C)
4. COOLING PRESSURE OVER RISE PROTECTION
On cooling mode, the compressor frequency is controlled as following based on the
detection value of the outdoor heat exchanger temperature sensor.
Outdoor heat exchange
temperature
( Fig.18 : Cooling pressure over rise protection control )
Compressor is OFF
The compressor frequency is
decreased 5rps every 120seconds.
Release of protection