02-10
Trouble shooting 7
INDOOR UNIT Error Method:
Connection unit number error (Indoor
unit in Wired remote controller system)
Detective Actuators:
Wired remote controller ( 2-Wire )
Indoor unit Controller PCB circuit
Detective details:
When the number of connecting indoor units are out of specified rule.
Forecast of Cause :
1. Wrong wiring / Number of I.U, RC in RCgroup 2. Indoor unit controller PCB defective
Check Point 1 : Wire installation
Wrong number of connecting indoor unit
Check Point 2 : Check Indoor unit controller PCB
Check if controller PCB damage
Check if controller PCB and check the Error after setting remote controller address
Indicate or Display:
Indoor Unit :
Operation lamp: 2 times Flash,
Timer lamp : 9 times Flash
ERROR CODE : [E : 29]
n
: n times blinking
: Light ON: Light OFF
Outdoor unit :
POWER
MODE
ERROR
2
5
(L1) (L2) (L6)(L5)(L4)(L3)
15
PUMP
DOWN
LOW
NOISE
PEAK
CUT