4-2. Heating capacity
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
¢
Model: AUXG09KVLA
AFR
m
3
/h
540
Indoor temperature
°CDB 16 18 20 22 24
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 3.35 1.26 3.27 1.28 3.19 1.31 3.11 1.34 3.03 1.36
-10 -11 3.71 1.31 3.62 1.33 3.53 1.36 3.44 1.39 3.35 1.41
-5 -7 4.06 1.35 3.97 1.38 3.87 1.41 3.77 1.44 3.68 1.47
0 -2 4.42 1.40 4.32 1.43 4.21 1.46 4.10 1.49 4.00 1.52
5 3 4.79 1.45 4.67 1.48 4.56 1.51 4.45 1.54 4.33 1.57
7 6 4.94 1.46 4.82 1.49 4.70 1.52 4.58 1.55 4.47 1.58
10 8 5.17 1.49 5.04 1.52 4.92 1.55 4.80 1.58 4.67 1.61
15 10 5.10 1.29 4.98 1.31 4.86 1.34 4.74 1.37 4.62 1.39
20 15 5.16 1.16 5.03 1.19 4.91 1.21 4.79 1.23 4.66 1.25
24 18 5.42 1.17 5.29 1.20 5.16 1.22 5.03 1.24 4.90 1.26
¢
Model: AUXG12KVLA
AFR
m
3
/h
600
Indoor temperature
°CDB 16 18 20 22 24
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 3.87 1.55 3.78 1.58 3.69 1.61 3.60 1.64 3.51 1.67
-10 -11 4.35 1.62 4.24 1.66 4.14 1.69 4.04 1.72 3.93 1.76
-5 -7 4.83 1.69 4.72 1.72 4.60 1.76 4.49 1.80 4.37 1.83
0 -2 5.31 1.76 5.19 1.79 5.06 1.83 4.93 1.87 4.81 1.90
5 3 5.79 1.82 5.65 1.86 5.51 1.90 5.37 1.94 5.23 1.98
7 6 5.99 1.84 5.84 1.88 5.70 1.92 5.56 1.96 5.42 2.00
10 8 6.13 1.80 5.99 1.84 5.84 1.88 5.69 1.92 5.55 1.96
15 10 6.37 1.74 6.22 1.77 6.07 1.81 5.92 1.85 5.77 1.87
20 15 6.15 1.43 6.01 1.46 5.86 1.49 5.71 1.52 5.57 1.54
24 18 6.09 1.27 5.95 1.29 5.80 1.32 5.66 1.35 5.51 1.37
¢
Model: AUXG14KVLA
AFR
m
3
/h
800
Indoor temperature
°CDB 16 18 20 22 24
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 4.54 1.81 4.43 1.85 4.32 1.89 4.21 1.93 4.10 1.97
-10 -11 5.05 1.86 4.93 1.90 4.81 1.94 4.69 1.98 4.57 2.02
-5 -7 5.58 1.91 5.44 1.95 5.31 1.99 5.18 2.03 5.04 2.07
0 -2 6.09 1.95 5.95 1.99 5.80 2.03 5.66 2.07 5.51 2.11
5 3 6.62 2.00 6.46 2.04 6.30 2.08 6.14 2.12 5.99 2.16
7 6 6.83 2.01 6.66 2.05 6.50 2.09 6.34 2.13 6.18 2.17
10 8 6.96 1.94 6.80 1.98 6.63 2.02 6.46 2.06 6.30 2.10
15 10 7.21 1.83 7.04 1.87 6.87 1.91 6.70 1.95 6.53 1.98
20 15 7.09 1.56 6.92 1.60 6.75 1.63 6.58 1.66 6.41 1.69
24 18 7.47 1.56 7.29 1.60 7.11 1.63 6.93 1.66 6.75 1.69
¢
Model: AUXG18KVLA
AFR
m
3
/h
800
Indoor temperature
°CDB 16 18 20 22 24
Outdoor temperature
°CDB °CWB
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
-15 -16 5.05 1.74 4.93 1.77 4.81 1.81 4.69 1.85 4.57 1.88
-10 -11 5.69 1.86 5.56 1.90 5.42 1.94 5.28 1.98 5.15 2.02
-5 -7 6.33 1.97 6.18 2.01 6.03 2.05 5.88 2.09 5.73 2.13
0 -2 6.97 2.08 6.81 2.13 6.64 2.17 6.47 2.21 6.31 2.26
5 3 7.61 2.20 7.43 2.24 7.25 2.29 7.07 2.34 6.89 2.38
7 6 7.88 2.24 7.69 2.28 7.50 2.33 7.31 2.38 7.13 2.42
10 8 8.51 2.32 8.30 2.37 8.10 2.42 7.90 2.47 7.70 2.52
15 10 8.46 2.04 8.26 2.09 8.06 2.13 7.86 2.17 7.66 2.20
20 15 7.96 1.61 7.77 1.65 7.58 1.68 7.39 1.71 7.20 1.74
24 18 8.40 1.60 8.20 1.64 8.00 1.67 7.80 1.70 7.60 1.73
- 11 -
4-2. Heating capacity
4. Capacity table
CASSETTE TYPE
AUXG09-22KVLA
CASSETTE TYPE
AUXG09-22KVLA

Table of Contents