Forced thermostat off function
Function
setting /
Rotary SW of External
input and output PCB
External input Input signal Command
60-00 / 2
External input and output
PCB
Input 1
Off → On Thermostat off
60-09 / B
60-10 / C
On → Off
Normal
operation
60-11 / D
On
Off
On
Off
Compressor
Room temp.
Set temp.
Input
NOTE: When the signal is received from another unit on the refrigerant circuit, there may be a
delay in thermostat off function at the unit.
Control output function
Function
setting /
Rotary SW of External
input and output PCB
External output Output signal Command
60-00 / 1, 2 Output of indoor unit CN47
Low → High Operation
High → Low Stop
60-00 / 1
External input and output
PCB
Output 1
Off → On Operation
60-09 / B
60-10 / C
On → Off Stop
60-11 / D
The output is low when the unit is stopped.
Operation
Stop
High
Low
CN47
On
Off
Output 1
Indoor unit
- 202 -
12-5. Ceiling type 12. External input and output
3-UNIT
MULTI-SPLIT TYPE
3-UNIT
MULTI-SPLIT TYPE