EasyManua.ls Logo

Fujitsu AOYG45KATA - Model: AOYG22 KATA

Fujitsu AOYG45KATA
113 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-2. Model: AOYG22KATA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20 25
Height difference H (m)
Indoor unit is higher than
outdoor unit *
1
20 0.932 0.930
15 0.953 0.950 0.947
10 0.983 0.968 0.966 0.962
7.5 0.988 0.987 0.972 0.970 0.966
5 0.992 0.992 0.991 0.976 0.974 0.970
0 1.000 1.000 0.999 0.984 0.982 0.978
Indoor unit is lower than
outdoor unit *
2
-5 1.000 1.000 0.999 0.984 0.982 0.978
-7.5 1.000 0.999 0.984 0.982 0.978
-10 0.999 0.984 0.982 0.978
-15 0.984 0.982 0.978
-20 0.982 0.978
HEATING
Pipe length (m)
5 7.5 10 15 20 25
Height difference H (m)
Indoor unit is higher than
outdoor unit *
1
20 0.894 0.867
15 0.920 0.894 0.867
10 0.982 0.920 0.894 0.867
7.5 1.000 0.982 0.920 0.894 0.867
5 1.000 1.000 0.982 0.920 0.894 0.867
0 1.000 1.000 0.982 0.920 0.894 0.867
Indoor unit is lower than
outdoor unit *
2
-5 0.995 0.995 0.977 0.916 0.889 0.862
-7.5 0.993 0.975 0.913 0.887 0.860
-10 0.972 0.911 0.885 0.858
-15 0.902 0.876 0.849
-20 0.863 0.834
- 83 -
6-2. Model: AOYG22KATA 6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYG18-45KATA
OUTDOOR UNIT
AOYG18-45KATA

Table of Contents

Other manuals for Fujitsu AOYG45KATA

Related product manuals