6-6. Model: AOYG45KATA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 20 30
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
30 0.900
20 0.937 0.915
10 0.973 0.952 0.931
7.5 0.988 0.977 0.956 0.934
5 0.992 0.992 0.981 0.960 0.938
0 1.000 1.000 0.989 0.967 0.945
Indoor unit is lower
than outdoor unit *2
-5 1.000 1.000 0.989 0.967 0.945
-7.5 1.000 0.989 0.967 0.945
-10 0.989 0.967 0.945
-20 0.967 0.945
-30 0.945
HEATING
Pipe length (m)
5 7.5 10 20 30
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
30 0.978
20 0.988 0.978
10 0.998 0.988 0.978
7.5 1.000 0.998 0.988 0.978
5 1.000 1.000 0.998 0.988 0.978
0 1.000 1.000 0.998 0.988 0.978
Indoor unit is lower
than outdoor unit *2
-5 0.995 0.995 0.993 0.983 0.973
-7.5 0.993 0.991 0.981 0.971
-10 0.988 0.978 0.968
-20 0.968 0.958
-30 0.949
- 87 -
6-6. Model: AOYG45KATA 6. Capacity compensation rate for pipe length and height difference