- 61 -
DUCT TYPE
ARYG18-54LHTBP
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ-
ment.
NOTE: Setting will not be changed if invalid numbers or setting values are selected.
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
2) Static pressure
Select the appropriate static pressure according to the installation conditions.
Function no. Functions
1)
11
Filter sign
2)
26
Static pressure
3)
30/31
Room temperature control for indoor unit sensor
4)
35/36
Room temperature control for wired remote controller sensor
5)
40
Auto restart
6)
42
Room temperature sensor switching
7)
43
Cold air prevention
8)
44
Remote controller custom code
9)
46
External input control
10)
48
Room temperature sensor switching (Aux.)
11)
49
Indoor unit fan control for energy saving for cooling
12)
60
Switching functions for external output terminal
Function number Setting value Setting description Factory setting
11
00 Standard (2,500 hours)
01 Long interval (4,400 hours)
02 Short interval (1,250 hours)
03 No indication
Function number Setting value Setting description Factory setting
26
03 30 Pa
04 40 Pa
05 50 Pa
06 60 Pa
07 70 Pa
08 80 Pa
09 90 Pa
10 100 Pa
11 110 Pa
12 120 Pa
13 130 Pa
14 140 Pa
15 150 Pa
16 160 Pa
17 170 Pa
18 180 Pa
19 190 Pa
20 200 Pa
31
Standard (35 Pa: 18, 24 type)
Standard (47 Pa: 30, 36 type)
Standard (60 Pa: 45, 54 type)
32 Automatic airflow adjustment