- 62 -
DUCT TYPE
ARYG18-54LHTBP
NOTE: Range of static pressure is different by model.
If the static pressure is set above maximum range, the setting will be the same as the maximum.
Example:
For 45, 54 type models, setting "170 Pa" (17) to "200 Pa" (20) will be the same as "160 Pa" (16).
For details, refer to Chapter 7. "Fan performance curve" on page 25.
3) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufactur-
er’s recommended value).
Type name Setting of static pressure range
18 type, 24 type, 30 type, and 36 type 30 to 200 Pa
45 type or 54 type 30 to 160 Pa
Function number Setting value Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00 Standard setting ♦
01 No correction 0.0 °C
02 -0.5 °C
More cooling
Less heating
03 -1.0 °C
04 -1.5 °C
05 -2.0 °C
06 -2.5 °C
07 -3.0 °C
08 -3.5 °C
09 -4.0 °C
10 +0.5 °C
Less cooling
More heating
11 +1.0 °C
12 +1.5 °C
13 +2.0 °C
14 +2.5 °C
15 +3.0 °C
16 +3.5 °C
17 +4.0 °C