( Fig.1 : Outdoor temperature zone )
1. COOLING OPERATION
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
Minimum
frequency
Maximum
frequency
Maximum
frequency
12rps
44rps
47rps
62rps
67rps
12rps 83rps58rps
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
Indoor fan mode
Me Lo Quiet
A zone 62rps 36rps 24rps 18rps
B zone 62rps 36rps 24rps 18rps
C zone 62rps 36rps 24rps 18rps
D zone 44rps 34rps 22rps 16rps
E zone 44rps 34rps 22rps 16rps
F zone 44rps 34rps 22rps 16rps
( Table 1 : Compressor frequency range )
01-01
E zone
F zone
10°C
0°C
12°C
2°C
* When the room temperature is between +6°C to -1°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Fig.1 based on the indoor
fan mode and the outdoor temperature.
* If the room temperature is some degrees lower than a set temperature,
the compressor will be stopped.
AO*G09KGCA
AO*G12KGCA
AO*G14KGCA
A zone 67rps 38rps 26rps 18rps
B zone 67rps 38rps 26rps 18rps
C zone 67rps 38rps 26rps 18rps
D zone 47rps 36rps 24rps 16rps
E zone 47rps 36rps 24rps 16rps
F zone 47rps 36rps 24rps 16rps
A zone 83rps 42rps 30rps 18rps
B zone 83rps 42rps 30rps 18rps
C zone 83rps 30rps 18rps
D zone 58rps 40rps 28rps 16rps
E zone 58rps 40rps 28rps 16rps
F zone 58rps 40rps 28rps 16rps
A zone 83rps 42rps 30rps 18rps
B zone 83rps 42rps 30rps 18rps
C zone 83rps 42rps 30rps 18rps
D zone 58rps 40rps 28rps 16rps
E zone 58rps 40rps 28rps 16rps
F zone 58rps 40rps 28rps 16rps
42rps
Outdoor
temperature
Outdoor
temperature
( Table 2 : Limit of maximum speed based on outdoor temperature )
AO*G07KGCA
AO*G09KGCA
AO*G07KGCA
AO*G12KGCA
AO*G14KGCA
Outdoor
temp. zone
Hi
* If the room temperature is 6°C higher than a set temperature, the compressor operation
frequency will attain to maximum performance.
When the compressor operates for 30 minutes continuously at over the maximum frequency ,
the maximum frequency is changed from Maximum Frequency to Maximum Frequency .