EasyManuals Logo

Fujitsu AS G07KGTA Series User Manual

Fujitsu AS G07KGTA Series
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
2. HEATING OPERATION
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is lower by 6°C than a set temperature, the compressor operation
frequency will attain to maximum performance.
* If the room temperature is some degrees higher than a set temperature,
the compressor will be stopped.
* When the room temperature is between +1°C to -6°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table 3.
( Table 3 : Compressor frequency range )
01-02
Minimum
frequency
Maximum
frequency
12rps 110rps
12rps 110rps
AO*G07KGCA
AO*G09KGCA
AO*G12KGCA
AO*G14KGCA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AS G07KGTA Series and is the answer not in the manual?

Fujitsu AS G07KGTA Series Specifications

General IconGeneral
BrandFujitsu
ModelAS G07KGTA Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals