3. DRY OPERATION
The compressor frequency shall change according to the temperature, set temperature,
and room temperature variation which the room temperature sensor of the indoor unit body has
detected as shown in the Table 4.
Ts+0.5°C
Ts -1.5°C
Ts -0.5°C
Ts+1.5°C
( Table 4 : Compressor frequency in Dry mode)
( Fig.2 : Compressor control based on room temperature )
Operating
frequency
22rps
16rps
0rps
X zone
J zone
Y zone
X zone
J zone
Y zone
Room
temperature
Room
temperature