2. HEATING OPERATION
2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation speed of the compressor.
* If the room temperature is lower by 3°C than a set temperature, the compressor operation
speed will attain to maximum performance.
* If the room temperature is higher 2.5°C than a set temperatire, the compressor will be stopped.
* When the room temperature is between +2.5°C to -3°C of the setting temperature,
the compressor speed is controlled within the range shown in Table2.
( Table 2 : Compressor speed range )
01-02
Minimum
speed
Maximum
speed
18rps 119rps
18rps 130rps
AO*G09LECAN
AO*G12LECAN