3. DRY OPERATION
3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to the temperature, set temperature,
and room temperature variation which the room temperature sensor of the indoor unit body has
detected as shown in the Table 3.
However, the compressor frequency after the start-up is 56rps for 80seconds.
Ts+0.5°C
Ts -1.5°C
Ts -0.5°C
Ts+1.5°C
( Table 3 : Compressor frequency )
( Fig.2 : Compressor control based on room temperature )
01-03
Operating
speed
30rps
23rps
0rps
09LECAN
X zone
J zone
Y zone
Operating
speed
J zone
Y zone
X zone
33rps
25rps
0rps
12LECAN
Room Room
temperature drops temperature rises
X zone
J zone
Y zone