6. Capacity table
6-1. Combinations
¢ Model: AOU24RLXFZ
Cooling
1) Non-ducted
Combination of indoor unit
Rated capacity for each indoor
unit (kBtu/h)
Maximum capacity for each in-
door unit (kBtu/h)
Total capacity
(kBtu/h)
Input power (kW)
Room 1 Room 2 Room 3 Total Room 1 Room 2 Room 3 Room 1 Room 2 Room 3 Min. Rated Max. Min. Rated Max.
7 7 - 14 7.05 7.05 - 8.70 8.70 - 6.10 14.10 17.40 0.50 1.20 1.51
7 9 - 16 7.09 9.11 - 8.66 11.14 - 6.10 16.20 19.80 0.50 1.36 1.78
7 12 - 19 7.07 12.13 - 8.33 14.27 - 6.10 19.20 22.60 0.50 1.63 2.20
7 15 - 22 6.87 13.73 - 8.05 16.10 - 6.10 20.60 24.15 0.50 1.70 2.54
7 18 - 25 6.16 15.84 - 7.20 18.50 - 6.10 22.00 25.70 0.50 1.76 2.87
9 9 - 18 9.00 9.00 - 10.75 10.75 - 6.10 18.00 21.50 0.50 1.55 2.02
9 12 - 21 9.00 12.00 - 10.11 13.49 - 6.10 21.00 23.60 0.50 1.73 2.45
9 15 - 24 8.41 13.09 - 9.70 15.10 - 6.10 21.50 24.80 0.50 1.75 2.66
9 18 - 27 7.33 14.67 - 8.67 17.33 - 6.10 22.00 26.00 0.50 1.76 2.87
12 12 - 24 11.00 11.00 - 12.50 12.50 - 6.10 22.00 25.00 0.50 1.74 2.74
12 15 - 27 10.15 11.85 - 12.46 14.54 - 6.10 22.00 27.00 0.50 1.75 2.87
7 7 7 21 7.00 7.00 7.00 8.57 8.57 8.57 6.10 21.00 25.70 0.50 1.75 2.47
7 7 9 23 6.70 6.70 8.61 8.22 8.22 10.57 6.10 22.00 27.00 0.50 1.76 2.60
7 7 12 26 5.92 5.92 10.15 7.27 7.27 12.46 6.10 22.00 27.00 0.50 1.76 2.87
7 9 9 25 6.16 7.92 7.92 7.56 9.72 9.72 6.10 22.00 27.00 0.50 1.76 2.87
9 9 9 27 7.33 7.33 7.33 9.00 9.00 9.00 6.10 22.00 27.00 0.50 1.77 2.87
2) Ducted
Combination of indoor unit
Rated capacity for each indoor
unit (kBtu/h)
Maximum capacity for each in-
door unit (kBtu/h)
Total capacity
(kBtu/h)
Input power (kW)
Room 1 Room 2 Room 3 Total Room 1 Room 2 Room 3 Room 1 Room 2 Room 3 Min. Rated Max. Min. Rated Max.
7 9 - 16 7.09 9.11 - 8.66 11.14 - 6.10 16.20 19.80 0.50 1.44 1.83
7 12 - 19 7.07 12.13 - 8.33 14.27 - 6.10 19.20 22.60 0.50 1.79 2.23
7 18 - 25 6.16 15.84 - 7.20 18.50 - 6.10 22.00 25.70 0.50 2.09 2.87
9 9 - 18 9.00 9.00 - 10.75 10.75 - 6.10 18.00 21.50 0.50 1.70 2.12
9 12 - 21 9.00 12.00 - 10.11 13.49 - 6.10 21.00 23.60 0.50 1.88 2.55
9 18 - 27 7.33 14.67 - 8.67 17.33 - 6.10 22.00 26.00 0.50 2.09 2.87
12 12 - 24 11.00 11.00 - 12.50 12.50 - 6.10 22.00 25.00 0.50 2.08 2.84
7 7 9 23 6.70 6.70 8.61 8.22 8.22 10.57 6.10 22.00 27.00 0.50 1.81 2.65
7 7 12 26 5.92 5.92 10.15 7.27 7.27 12.46 6.10 22.00 27.00 0.50 2.11 2.87
7 9 9 25 6.16 7.92 7.92 7.56 9.72 9.72 6.10 22.00 27.00 0.50 2.11 2.87
9 9 9 27 7.33 7.33 7.33 9.00 9.00 9.00 6.10 22.00 27.00 0.50 2.12 2.87
NOTES:
Specifications are based on the following conditions.
Power source of specifications: 230 V
7: 7,000 Btu/h, 9: 9,000 Btu/h, 12: 12,000 Btu/h, 15: 14,000 Btu/h, 18: 18,000 Btu/h
2 or more indoor units should be connected.
Cooling: Indoor temperature of 80 °FDB (26.7 °CDB)/ 67 °FWB (19.4 °CWB), and outdoor tem-
perature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB).
Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit—Indoor unit]
The total ability of connected indoor units is from 14,000 Btu up to 27,000 Btu.
Non-Ducted system combinations input are based on wall mount models. The input of combina-
tions including cassette models may be a little higher.
Ducted system combinations capacities are based on slim duct units excepting 7,000-Btu mod-
els. 7,000 Btu models are based on wall mount models.
¢
Model: AOU24RLXFZ
- 213 -
6-1. Combinations 6. Capacity table
OUTDOOR UNIT
AOU24RLXFZ
OUTDOOR UNIT
AOU24RLXFZ

Table of Contents

Other manuals for Fujitsu ASU18RLF

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASU18RLF and is the answer not in the manual?

Fujitsu ASU18RLF Specifications

General IconGeneral
BrandFujitsu
ModelASU18RLF
CategoryAir Conditioner
LanguageEnglish

Related product manuals