EasyManua.ls Logo

Fujitsu ASYG07KGTA - Capacity Compensation Rate for Pipe Length and Height Difference; Models: AOYG07 KGCA, AOYG09 KGCA, AOYG12 KGCA, and AOYG14 KGCA

Fujitsu ASYG07KGTA
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HH
6-1. Models: AOYG07KGCA, AOYG09KGCA, AOYG12KGCA,
and AOYG14KGCA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 0.858 0.868
10 0.929 0.872 0.882
7.5 0.960 0.933 0.876 0.885
5 0.992 0.964 0.937 0.879 0.889
0 1.000 0.972 0.944 0.887 0.896
Indoor unit is lower than
outdoor unit *2
-5 1.000 0.972 0.944 0.887 0.896
-7.5 0.972 0.944 0.887 0.896
-10 0.944 0.887 0.896
-15 0.887 0.896
HEATING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 0.896 0.879
10 0.968 0.890 0.879
7.5 0.994 0.968 0.896 0.879
5 1.000 0.994 0.968 0.896 0.879
0 1.000 0.994 0.968 0.896 0.879
Indoor unit is lower than
outdoor unit *2
-5 0.995 0.989 0.963 0.891 0.875
-7.5 0.987 0.961 0.889 0.873
-10 0.959 0.887 0.871
-15 0.878 0.862
- 51 -
OUTDOOR UNIT
AOYG07-14KGCA

Table of Contents

Other manuals for Fujitsu ASYG07KGTA

Related product manuals